KL3112, KL3122 - Contact assignment and LEDs

WARNING

Risk of injury through electric shock and damage to the device!

Bring the Bus Terminal system into a safe, voltage-free state before starting mounting, disassembly or wiring of the Bus Terminals!

KL3112, KL3122 - Contact assignment and LEDs 1:
KL3112, KL3122 - Contact assignment and LEDs

KL3112/KS3112, KL3122/KS3122 - Contact assignment

Terminal point

No.

Comment

+Input 1

1

+ Input 1

-Input 1

2

- Input 1

GND

3

Internal ground (internally connected to terminal point 7)

Shield

4

PE contact (internally connected to terminal point 8)

+Input 2

5

+ Input 2

-Input 2

6

- Input 2

GND

7

Internal ground (internally connected to terminal point 3)

Shield

8

PE contact (internally connected to terminal point 4)

KL3112/KS3112, KL3122/KS3122 - LEDs

LED

Color

Description

Run LED1
Run LED2

green

On

Normal operation

Off

Watchdog timer overflow has occurred. If no process data is transmitted to the Bus Coupler for 100 ms, the green LEDs go out

Error LED1
Error LED2

red

On

Measured current outside the measuring range (> 20 mA)

Off

Current in valid range