KL302x/KS302x - Contact assignment and LEDs
Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or wiring of the Bus Terminals!
Contact assignment of KL3021/KS3021 | ||
---|---|---|
Terminal point | No. | Comment |
+Input 1 | 1 | + Input 1 |
-Input 1 | 2 | - Input 1 |
GND | 3 | Internal ground (internally connected to terminal point 7) |
Shield | 4 | PE contact (internally connected to terminal point 8) |
n.c. | 5 | not connected |
n.c. | 6 | not connected |
GND | 7 | Internal ground (internally connected to terminal point 3) |
Shield | 8 | PE contact (internally connected to terminal point 4) |
Contact assignment of KL3022/KS3022 | ||
---|---|---|
Terminal point | No. | Comment |
+Input 1 | 1 | + Input 1 |
-Input 1 | 2 | - Input 1 |
GND | 3 | Internal ground (internally connected to terminal point 7) |
Shield | 4 | PE contact (internally connected to terminal point 8) |
+Input 2 | 5 | + Input 2 |
-Input 2 | 6 | - Input 2 |
GND | 7 | Internal ground (internally connected to terminal point 3) |
Shield | 8 | PE contact (internally connected to terminal point 4) |
KL302x/KS302x - LED display | |||
---|---|---|---|
LED | Color | Description | |
Run1 LED | green | On: | Normal operation |
Off: | Watchdog-timer overflow has occurred. If no process data is transmitted to the bus coupler for 100 ms, the green LEDs go out | ||
Error1 LED | red | On: | The limit stop of the A/D converter has been reached. The current is greater than 21.5 mA. |
Off: | Normal operation |