Technical data

Technical data

KL2828

Connection technology

2 wire

Number of outputs

8

Rated load voltage

24 VDC (-15% / +20%)

Load type

ohmic, inductive, capacitive

Output current

max. 2 A per channel (∑ max. 10 A)

Short circuit current

< 40 A typ.

Breaking energy

< 1.2 J/channel

Reverse voltage protection

yes

Current consumption K-bus

typ. 18 mA

Current consumption of power contacts

typ. 15 mA + load

Electrical isolation

500 V (K-bus/field potential)

Bit width in process image

8 output bits

Configuration

no address or configuration settings required

Dimensions (W x H x D)

app. 15 mm x 100 mm x 70 mm (aligned width 12 mm)

Weight

app. 70 g

Mounting

on 35 mm mounting rail according to EN 60715

Permissible ambient temperature range during operation

-25°C … +60°C (extended temperature range)

Permissible ambient temperature range during storage

-40°C ... +85°C

Permissible relative humidity

95%, no condensation

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27, see also Installation instructions for enhanced mechanical load capacity

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Installation position

variable, see chapter Installation positions

Protection class

IP20

Approvals / markings

CE, cULus