KL2798 - HD Bus Terminal 8-channel digital output 30 V AC/DC

Technical data

 

KL2798 - Technical data

Technical data
KL2798-0000
Connection technology
2-wire
Number of outputs
8 x make contacts
Rated load voltage
0…30 V AC/DC (only ohmic load: 0…48 V DC)
Max. output current
2 A per channel (∑ 10 A)
Breakdown voltage
80 V
Peak current
5 A (100 ms), < 50 A (10 ms)
Short circuit current
not short-circuit-proof, see peak current
Reverse voltage protection
Isolation voltage (channel/channel)
< 200 V
Electrical isolation
500 V (K-bus/field potential)
Switching on speed
typ. 1.8 ms, max. 5 ms
Switching off speed
typ. 30 ms, max. 50 ms
On-resistance
typ. 0.03 Ω
Current consumption power contacts
Current consumption K-bus
80 mA
Bit width in the process image
8 output bits
Special features
substitute for relay contacts, potential-free
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Weight
approx. 50 g
on 35 mm mounting rail according to EN 60715
Operating temperature
0…+55 °C
Storage temperature
-25…+85 °C
Relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Installation pos.
variable
Protect. class
IP 20
Approvals
CE, UL