KL2602, KL2622, KL2634 - Two-and four-channel Relay Output Terminals

KL2634-0000 - Connector pin assignment and LEDs

 
 
 SmallWarningYellow CAUTION
Risk of injury!
Bring the bus system into a safe, powered down state before starting installation, disassembly or wiring of the Bus Terminals!
Note
Possible damage of devices!
When designing a Bus Terminal block with different potentials on the power contacts (e.g. 230 VAC and 24 VDC), please note that it is mandatory to use potential separation terminals (e.g.: KL9080)!
 
 KL2634_intro
KL2634-0000
 
LED displays KL2634-0000
LED
Color
State
Meaning
Signal 1…Signal 4
green
off
Contacts 1-2 (Channel 1), 5-6 (Channel 2), 3-4 (Channel 3 ) or 7-8 (Channel 4) not connected
on
Contacts 1-2 (Channel 1), 5-6 (Channel 2), 3-4 (Channel 3 ) or 7-8 (Channel 4) connected
 
 
Pin assignment KL2634-0000
Terminal point
Description
Name
No.
13
1
Relay 1, NO contact
14
2
33
3
Relay 3, NO contact
34
4
23
5
Relay 2, NO contact
24
6
43
7
Relay 4, NO contact
44
8