KL2602, KL2622, KL2634 - Two-and four-channel Relay Output Terminals

KL2622-00x0 - Connector pin assignment and LEDs

 
 
 SmallWarningYellow CAUTION
Risk of injury!
Bring the bus system into a safe, powered down state before starting installation, disassembly or wiring of the Bus Terminals!
Note
Possible damage of devices!
When designing a Bus Terminal block with different potentials on the power contacts (e.g. 230 VAC and 24 VDC), please note that it is mandatory to use potential separation terminals (e.g.: KL9080)!
 
 kl2622_kl2622-0010_intro
KL2622-0000 and KL2622-0010
 
LED displays KL2622-0000 and KL2622-0010
LED
Color
State
Meaning
Signal 1,
Signal 2
green
off
Contacts 1-2 (Channel 1) and 5-6 respectively (Channel 2) not connected i.e. no voltage on output 1 and output 2 respectively
on
Contacts 1-2 (Channel 1) and 5-6 respectively (Channel 2) connected
i.e. output voltage (≤ 230 VAC or ≤ 30 VDC) on output 1 and output 2 respectively
Status
KL2622-0010 only
green
off
Terminal not synchronized (relay switches without delay e.g. by DC supply)
on
Terminal is synchronized on mains frequency
 
 
Pin assignment KL2622-0000 and KL2622-0010
Terminal
Terminal point
Description
Name
No.
KL2622-0000, KL2622-0010
01
1
Output 1 (relay)
L1
2
120 / 230 VAC
KL2622-0000
-
3
not connected
KL2622-0010
N
Neutral line (internal connected with terminal point 7)
KL2622-0000, KL2622-0010
PE
4
PE (internal connected with terminal point 8 and PE power contact)
02
5
Output 2 (relay)
L1
6
120 / 230 VAC
KL2622-0000
-
7
not connected
KL2622-0010
N
Neutral line (internal connected with terminal point 3)
KL2622-0000, KL2622-0010
PE
8
PE (internal connected with terminal point 4 and PE power contact)