KL2602, KL2622, KL2634 - Two-and four-channel Relay Output Terminals

KL2602-00x0 - Connector pin assignment and LEDs

 
 
 SmallWarningYellow CAUTION
Risk of injury!
Bring the bus system into a safe, powered down state before starting installation, disassembly or wiring of the Bus Terminals!
Note
Possible damage of devices!
When designing a Bus Terminal block with different potentials on the power contacts (e.g. 230 VAC and 24 VDC), please note that it is mandatory to use potential separation terminals (e.g.: KL9080)!
 
 kl2602_kl2602-0010_intro_en
KL2602-0000 and KL2602-0010
 
LED displays KL2602-0000, KL2602-0010
LED
Color
State
Meaning
Signal 1,
Signal 2
green
off
No voltage on output 1 and output 2 respectively
on
Output voltage (≤ 230 VAC or ≤ 30 VDC) on output 1 and output 2 respectively
Status
(KL2602-0010 only)
green
off
Terminal not synchronized (relay switches without delay e.g. by DC supply)
on
Terminal is synchronized on mains frequency
 
 
Pin assignment KL2602-0000, KL2602-0010
Terminal point
Description
Name
No.
01
1
Output 1 (relay)
L1
2
120 / 230 VAC (internal connected with terminal point 6 and L power contact)
N
3
Neutral line (internal connected with terminal point 7 and N power contact)
PE
4
PE (internal connected with terminal point 8 and PE power contact)
02
5
Output 2 (relay)
L1
6
120 / 230 VAC (internal connected with terminal point 2 and L power contact)
N
7
Neutral line (internal connected with terminal point 3 and N power contact)
PE
8
PE (internal connected with terminal point 4 and PE power contact)