KL2602, KL2622, KL2634 - Two-and four-channel Relay Output Terminals

KL2602-00x0, KL2622-00x0 - Technical data

 

KL2602-0000 and KL2622-0000

 
Technical data
KL2602-0000
KL2622-0000
Number of outputs
2 N/O contacts for power contact
2 N/O contacts (potential free)
Contact material
AgCdO
Switching voltage
max. 250 VAC / 30 VDC
Switching current
Max. 5 A
Switching capacity max. with resistive load
Alternating voltage:
5 A   250 VAC 1250 VA
Direct voltage:
5 A   30 VDC 150 W
Maximum switching current
with inductive load, cosφ=0.4, L/R=7ms
2 A   250 VAC
2 A   30 VDC
Minimum permitted load (approximate)
10 mA at 5 VDC (as supplied)
100 mA at 5 VDC   (after a current of approx. 100 mA
(or greater) has been switched at least once)
Reaction time at a rated load
Reaction time: max. 10 ms
Release time: max. 4 ms
Bounce time: max. 5 ms
Electrical isolation
500 V (K-Bus / mains voltage)
K-Bus current consumption
80 mA
85 mA
Bit width in process image
2 outputs
Service life Mechanical operating cycles
20,000,000 switching operations
Service life Electrical operating cycles
At least 100,000 switching operations on resistive loads at
   250 VAC   5 A or
   30 VDC   5 A
Permitted switching frequency at maximum contact load
10 switching operations / minute
Contact resistance max. (new)
< 30 mΩ
Insulation resistance (min).
100 MΩ at 500 VDC
Test voltage between open contacts
750 V (1 minute between open contacts)
Configuration
no address or configuration settings
Weight
approx. 85 g
approx. 80 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail according to EN 60715
Permissible ambient temperature range during operation
-25°C…+60°C
Permissible ambient temperature range during storage
-40°C ... +85°C
Permissible relative humidity
95 %, no condensation
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Installation position
Variable
Protect. class
IP20
Approvals
CE, cULus, ATEX, GL
 
 

KL2602-0010 and KL2622-0010

 
Technical data
KL2602-0010
KL2622-0010
Number of outputs
2 x make contacts for power contact
2 x make contacts
Contact material
Ag-Alloy (Au plating applied to stationary contact)
Rated load voltage
230 VAC / 30 VDC
Load type
ohmic, inductive, capacitive
Switching current max.
typ. 5 AAC/DC each channel
Switching current inductive
typ. 2 AAC/DC each channel
Minimal permissible load
typ. 0.1 mA at 0.1 VDC
Electrical isolation
500 V (K-bus/field potential)
K-Bus current consumption
80 mA
85 mA
Bit width in the process image
2 outputs
Reaction time at a rated load
max. 20 ms (= 10 ms zero crossing voltage delay at 50 Hz + 10 ms delay time of the relay)
Operating cycles mech. (min.)
2 x 107 (at 18 x 103 switching cycles per hour)
Operating cycles electr. (min.)
100,000 (3 A at 250 VAC, 3 A at 30 VDC and ohmic load)
80,000 (5 A at 250 VAC, 5 A at 30 VDC and ohmic load)
100,000 (2 A at 250 VAC, 2 A at 30 VDC and inductive load)
Configuration
no address or configuration settings
Special features
Soft switching at the zero voltage crossing
Contact resistance (max.)
typ. 100 mΩ
Insulation resistance (min.)
typ. 1000 MΩ at 500 VDC
Weight
approx. 50 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Permissible ambient temperature range during operation
0…+55 °C
Permissible ambient temperature range during storage
-25…+85 °C
Permissible relative humidity
95 %, no condensation
on 35 mm mounting rail according to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4
Installation position
Variable
Protect. class
IP20
Approvals
CE, cULus