KL2552 - LED displays

KL2552 - LED displays 1:
KL2552 - LEDs

Left LED prism

LED

Display

Run (green)

on

Data transmission on the K-bus is active

Enc. A: A (green)

on

There is a signal at input A for encoder A.

Enc. B: A (green)

on

There is a signal at input A for encoder B.

Input 1 (green)

on

There is a signal at input 1.

Enc. Rdy. (green)

on

Encoder evaluation ready to operate.

Enc. A: B (green)

on

There is a signal at input B for encoder A.

Enc. B: B (green)

on

There is a signal at input B for encoder B.

Input 2 (green)

on

There is a signal at input 2.

Right LED prism

LED

Display

Drv. Rdy. (green)

on

Motor driver ready to operate.

Enable A (green)

off

Channel 1 is either not enabled or not ready to operate.

on

Channel 1 is enabled and is ready to operate.

Warning A (yellow)

on

Warning of channel 1

Error A (red)

on

There is an error at channel 1

Power (green)

off

The motor supply voltage is not available.

on

The motor supply voltage is available.

Enable B (green)

off

Channel 2 is either not enabled or not ready to operate.

on

Channel 2 is enabled and is ready to operate.

Warning B (yellow)

on

Warning of channel 2

Error B (red)

on

There is an error at channel 2