UL Requirements

The installation of the Fieldbus Box Modules certified by UL has to meet the following requirements.

Supply voltage

Note
  • by a 24 VDC supply voltage, supplied by an isolating source and protected by means of a fuse (in accordance with UL248), rated maximum 4 Amp, or
  • by a 24 VDC power source, that has to satisfy NEC class 2.
    A NEC class 2 power supply shall not be connected in series or parallel with another (class 2) power source!
Note
Warning

To meet the UL requirements, the Fieldbus Box Modules must not be connected to unlimited power sources!

Networks

Note
Warning

To meet the UL requirements, Fieldbus Box Modules must not be connected to telecommunication networks!

Ambient temperature range

Note
Warning

To meet the UL requirements, Fieldbus Box Modules have to be operated only at an ambient temperature range of  0 to 55°C!

Marking for UL

All Fieldbus Box Modules certified by UL (Underwriters Laboratories) are marked with the following label.