Technical data
Technical data | EPP1332-0001 | EPP1342-0001 |
---|---|---|
Task in the EtherCAT system | 3-port EtherCAT P junction and refresh for US and UP | 3-port EtherCAT P junction |
Fieldbus | EtherCAT | |
Bus interface | M8 socket, shielded, screw-type, 4-pin, EtherCAT P-coded | |
Number of channels | IN: 1 x EtherCAT P, OUT: 3 x EtherCAT P | IN: 1 x EtherCAT P, OUT: 3 x EtherCAT P |
Nominal input voltage | 24 VDC (-15%/+20%) | |
Sum current | Max. current 3 A per US and UP | no power supply |
Power supply connection | feed: | not required |
Current carrying capacity per | max. 3 A per US and UP | |
Supply of the module electronics | From the control voltage US, | From the control voltage US, |
Current consumption of the module electronics | typically 65 mA + load | |
Permissible ambient temperature during operation | -25 °C to +60 °C | |
Permissible ambient temperature during storage | -40 °C to +85 °C | |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27; | |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 | |
Protection class | IP65, IP66, IP67 (conforms to EN 60529) | |
Mounting position | variable | |
Approvals | CE, cULus |
Additional checks
The boxes have been subjected to the following checks:
Verification | Explanation |
---|---|
Vibration | 10 frequency sweeps in 3 axes |
5 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude | |
60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude | |
Shocks | 1000 shocks in each direction, in 3 axes |
35 g, 11 ms |