Object overview

Object overview 1:

EtherCAT XML Device Description

The display matches that of the CoE objects from the EtherCAT XML Device Description. We recommend downloading the latest XML file from the download area of the Beckhoff website and installing it according to installation instructions.

Index (hex)

Name

Flags

Default value

1000

Device type

RO

0x00001389 (5001dec)

1008

Device name

RO

EP8309-1022

1009

Hardware version

RO

00

100A

Software version

RO

02

1011:0

Subindex

Restore default parameters

RO

0x01 (1dec)

1011:01

SubIndex 001

RW

0x00000000 (0dec)

1018:0

Subindex

Identity

RO

0x04 (4dec)

1018:01

Vendor ID

RO

0x00000002 (2dec)

1018:02

Product code

RO

0x20754052 (544555090dec)

1018:03

Revision

RO

0x00110016 (1114134dec)

1018:04

Serial number

RO

0x00000000 (0dec)

10F0:0

Subindex

Backup parameter handling

RO

0x01 (1dec)

10F0:01

Checksum

RO

0x00000000 (0dec)

1402:0

Subindex

PWM RxPDO-Par Control

RO

0x06 (6dec)

1402:06

Exclude RxPDOs

RO

03 16

1403:0

Subindex

AO RxPDO-Par Outputs

RO

0x06 (6dec)

1403:06

Exclude RxPDOs

RO

02 16

1600:0

Subindex

TACHO RxPDO-Map OutputsCh.1

RO

0x03 (3dec)

1600:01

SubIndex 001

RO

0x0000:00, 8

1600:02

SubIndex 002

RO

0x7020:09, 1

1600:03

SubIndex 003

RO

0x0000:00, 7

1601:0

Subindex

DO RxPDO-Map Outputs

RO

0x07 (7dec)

1601:01

SubIndex 001

RO

0x7050:01, 1

1601:02

SubIndex 002

RO

0x7050:02, 1

1601:03

SubIndex 003

RO

0x7050:03, 1

1601:04

SubIndex 004

RO

0x7050:04, 1

1601:05

SubIndex 005

RO

0x7050:05, 1

1601:06

SubIndex 006

RO

0x7050:06, 1

1601:07

SubIndex 007

RO

0x0000:00, 10

1602:0

Subindex

PWM RxPDO-Map Control

RO

0x06 (6dec)

1602:01

SubIndex 001

RO

0x7060:01, 1

1602:02

SubIndex 002

RO

0x0000:00, 4

1602:03

SubIndex 003

RO

0x7060:06, 1

1602:04

SubIndex 004

RO

0x7060:07, 1

1602:05

SubIndex 005

RO

0x0000:00, 9

1602:06

SubIndex 006

RO

0x7060:11, 16

Index (hex)

Name

Flags

Default value

1603:0

Subindex

AO RxPDO-Map Outputs

RO

0x01 (1dec)

1603:01

SubIndex 001

RO

0x7070:11, 16

1802:0

Subindex

TACHO TxPDO-Par Single Shaft Mode Input Ch.1

RO

0x06 (6dec)

1802:06

Exclude TxPDOs

RO

03 1A 04 1A

1803:0

Subindex

TACHO TxPDO-Par Dual Shaft Mode Input Ch.1

RO

0x06 (6dec)

1803:06

Exclude TxPDOs

RO

02 1A 00 00

1804:0

Subindex

TACHO TxPDO-Par Dual Shaft Mode Input Ch.2

RO

0x06 (6dec)

1804:06

Exclude TxPDOs

RO

02 1A 00 00

1A00:0

Subindex

AI TxPDO-Map Inputs Ch.1

RO

0x0A (10dec)

1A00:01

SubIndex 001

RO

0x6000:01, 1

1A00:02

SubIndex 002

RO

0x6000:02, 1

1A00:03

SubIndex 003

RO

0x6000:03, 2

1A00:04

SubIndex 004

RO

0x6000:05, 2

1A00:05

SubIndex 005

RO

0x6000:07, 1

1A00:06

SubIndex 006

RO

0x0000:00, 6

1A00:07

SubIndex 007

RO

0x6000:0E, 1

1A00:08

SubIndex 008

RO

0x6000:0F, 1

1A00:09

SubIndex 009

RO

0x6000:10, 1

1A00:0A

SubIndex 010

RO

0x6000:11, 16

1A01:0

Subindex

AI TxPDO-Map Inputs Ch.2

RO

0x0A (10dec)

1A01:01

SubIndex 001

RO

0x6010:01, 1

1A01:02

SubIndex 002

RO

0x6010:02, 1

1A01:03

SubIndex 003

RO

0x6010:03, 2

1A01:04

SubIndex 004

RO

0x6010:05, 2

1A01:05

SubIndex 005

RO

0x6010:07, 1

1A01:06

SubIndex 006

RO

0x0000:00, 6

1A01:07

SubIndex 007

RO

0x6010:0E, 1

1A01:08

SubIndex 008

RO

0x6010:0F, 1

1A01:09

SubIndex 009

RO

0x6010:10, 1

1A01:0A

SubIndex 010

RO

0x6010:11, 16

1A02:0

Subindex

TACHO TxPDO-Map Single Shaft Mode Input Ch.1

RO

0x0C (12dec)

1A02:01

SubIndex 001

RO

0x0000:00, 1

1A02:02

SubIndex 002

RO

0x6037:02, 1

1A02:03

SubIndex 003

RO

0x6037:03, 1

1A02:04

SubIndex 004

RO

0x6037:04, 1

1A02:05

SubIndex 005

RO

0x6037:05, 1

1A02:06

SubIndex 006

RO

0x0000:00, 3

1A02:07

SubIndex 007

RO

0x0000:00, 3

1A02:08

SubIndex 008

RO

0x6037:0C, 1

1A02:09

SubIndex 009

RO

0x0000:00, 3

1A02:0A

SubIndex 010

RO

0x6037:10, 1

1A02:0B

SubIndex 011

RO

0x6037:11, 16

1A02:0C

SubIndex 012

RO

0x6037:12, 16

Index (hex)

Name

Flags

Default value

1A03:0

Subindex

TACHO TxPDO-Map Dual Shaft Mode Input Ch.1

RO

0x09 (9dec)

1A03:01

SubIndex 001

RO

0x6020:01, 1

1A03:02

SubIndex 002

RO

0x0000:00, 2

1A03:03

SubIndex 003

RO

0x0000:00, 1

1A03:04

SubIndex 004

RO

0x0000:00, 4

1A03:05

SubIndex 005

RO

0x0000:00, 3

1A03:06

SubIndex 006

RO

0x6020:0C, 1

1A03:07

SubIndex 007

RO

0x0000:00, 3

1A03:08

SubIndex 008

RO

0x6020:10, 1

1A03:09

SubIndex 009

RO

0x6020:11, 16

1A04:0

Subindex

TACHO TxPDO-Map Dual Shaft Mode Input Ch.2

RO

0x09 (9dec)

1A04:01

SubIndex 001

RO

0x6030:01, 1

1A04:02

SubIndex 002

RO

0x0000:00, 2

1A04:03

SubIndex 003

RO

0x0000:00, 1

1A04:04

SubIndex 004

RO

0x0000:00, 4

1A04:05

SubIndex 005

RO

0x0000:00, 3

1A04:06

SubIndex 006

RO

0x6030:0C, 1

1A04:07

SubIndex 007

RO

0x0000:00, 3

1A04:08

SubIndex 008

RO

0x6030:10, 1

1A04:09

SubIndex 009

RO

0x6030:11, 16

1A05:0

Subindex

DI TxPDO-Map Inputs

RO

0x07 (7dec)

1A05:01

SubIndex 001

RO

0x6040:01, 1

1A05:02

SubIndex 002

RO

0x6040:02, 1

1A05:03

SubIndex 003

RO

0x6040:03, 1

1A05:04

SubIndex 004

RO

0x6040:04, 1

1A05:05

SubIndex 005

RO

0x6040:05, 1

1A05:06

SubIndex 006

RO

0x6040:06, 1

1A05:07

SubIndex 007

RO

0x0000:00, 10

1A06:0

Subindex

PWM TxPDO-Map Status

RO

0x08 (8dec)

1A06:01

SubIndex 001

RO

0x0000:00, 1

1A06:02

SubIndex 002

RO

0x0000:00, 3

1A06:03

SubIndex 003

RO

0x6060:05, 1

1A06:04

SubIndex 004

RO

0x6060:06, 1

1A06:05

SubIndex 005

RO

0x6060:07, 1

1A06:06

SubIndex 006

RO

0x0000:00, 1

1A06:07

SubIndex 007

RO

0x0000:00, 7

1A06:08

SubIndex 008

RO

0x6060:10, 1

1A07:0

Subindex

PWM TxPDO-Map Synchron info data

RO

0x02 (2dec)

1A07:01

SubIndex 001

RO

0x6060:11, 16

1A07:02

SubIndex 002

RO

0x6060:12, 16

1C00:0

Subindex

Sync manager type

RO

0x04 (4dec)

1C00:01

SubIndex 001

RO

0x01 (1dec)

1C00:02

SubIndex 002

RO

0x02 (2dec)

1C00:03

SubIndex 003

RO

0x03 (3dec)

1C00:04

SubIndex 004

RO

0x04 (4dec)

Index (hex)

Name

Flags

Default value

1C12:0

Subindex

RxPDO assign

RW

0x03 (3dec)

1C12:01

SubIndex 001

RW

0x1600 (5632dec)

1C12:02

SubIndex 002

RW

0x1601 (5633dec)

1C12:03

SubIndex 003

RW

0x1602 (5634dec)

1C12:04

SubIndex 004

RW

0x0000 (0dec)

1C13:0

Subindex

TxPDO assign

RW

0x05 (5dec)

1C13:01

SubIndex 001

RW

0x1A00 (6656dec)

1C13:02

SubIndex 002

RW

0x1A01 (6657dec)

1C13:03

SubIndex 003

RW

0x1A02 (6658dec)

1C13:04

SubIndex 004

RW

0x1A05 (6661dec)

1C13:05

SubIndex 005

RW

0x1A06 (6662dec)

1C13:06

SubIndex 006

RW

0x0000 (0dec)

1C13:07

SubIndex 007

RW

0x0000 (0dec)

1C32:0

Subindex

SM output parameter

RO

0x20 (32dec)

1C32:01

Sync mode

RW

0x0001 (1dec)

1C32:02

Cycle time

RW

0x000F4240 (1000000dec)

1C32:03

Shift time

RO

0x00000000 (0dec)

1C32:04

Sync modes supported

RO

0xC007 (49159dec)

1C32:05

Minimum cycle time

RO

0x0007A120 (500000dec)

1C32:06

Calc and copy time

RO

0x00000000 (0dec)

1C32:07

Minimum delay time

RO

0x00000000 (0dec)

1C32:08

Command

RW

0x0000 (0dec)

1C32:09

Maximum delay time

RO

0x00000000 (0dec)

1C32:0B

SM event missed counter

RO

0x0000 (0dec)

1C32:0C

Cycle exceeded counter

RO

0x0000 (0dec)

1C32:0D

Shift too short counter

RO

0x0000 (0dec)

1C32:20

Sync error

RO

0x00 (0dec)

1C33:0

Subindex

SM input parameter

RO

0x20 (32dec)

1C33:01

Sync mode

RW

0x0022 (34dec)

1C33:02

Cycle time

RW

0x000F4240 (1000000dec)

1C33:03

Shift time

RO

0x00000000 (0dec)

1C33:04

Sync modes supported

RO

0xC007 (49159dec)

1C33:05

Minimum cycle time

RO

0x0007A120 (500000dec)

1C33:06

Calc and copy time

RO

0x00000000 (0dec)

1C33:07

Minimum delay time

RO

0x00000000 (0dec)

1C33:08

Command

RW

0x0000 (0dec)

1C33:09

Maximum delay time

RO

0x00000000 (0dec)

1C33:0B

SM event missed counter

RO

0x0000 (0dec)

1C33:0C

Cycle exceeded counter

RO

0x0000 (0dec)

1C33:0D

Shift too short counter

RO

0x0000 (0dec)

1C33:20

Sync error

RO

0x00 (0dec)

Index (hex)

Name

Flags

Default value

6000:0

Subindex

AI Inputs Ch.1

RO

0x11 (17dec)

6000:01

Underrange

RO

0x00 (0dec)

6000:02

Overrange

RO

0x00 (0dec)

6000:03

Limit 1

RO

0x00 (0dec)

6000:05

Limit 2

RO

0x00 (0dec)

6000:07

Error

RO

0x00 (0dec)

6000:0E

Sync error

RO

0x00 (0dec)

6000:0F

TxPDO State

RO

0x00 (0dec)

6000:10

TxPDO Toggle

RO

0x00 (0dec)

6000:11

Value

RO

0x0000 (0dec)

6010:0

Subindex

AI Inputs Ch.2

RO

0x11 (17dec)

6010:01

Underrange

RO

0x00 (0dec)

6010:02

Overrange

RO

0x00 (0dec)

6010:03

Limit 1

RO

0x00 (0dec)

6010:05

Limit 2

RO

0x00 (0dec)

6010:07

Error

RO

0x00 (0dec)

6010:0E

Sync error

RO

0x00 (0dec)

6010:0F

TxPDO State

RO

0x00 (0dec)

6010:10

TxPDO Toggle

RO

0x00 (0dec)

6010:11

Value

RO

0x0000 (0dec)

6020:0

Subindex

TACHO Dual Shaft Mode Input Ch.1

RO

0x11 (17dec)

6020:01

Digital Input

RO

0x00 (0dec)

6020:0C

Speed Below Threshold

RO

0x00 (0dec)

6020:10

TxPDO Toggle

RO

0x00 (0dec)

6020:11

Rotational Speed

RO

0x0000 (0dec)

6030:0

Subindex

TACHO Dual Shaft Mode Input Ch.2

RO

0x11 (17dec)

6030:01

Digital Input

RO

0x00 (0dec)

6030:0C

Speed Below Threshold

RO

0x00 (0dec)

6030:10

TxPDO Toggle

RO

0x00 (0dec)

6030:11

Rotational Speed

RO

0x0000 (0dec)

6037:0

Subindex

TACHO Single Shaft Mode Input

RO

0x12 (18dec)

6037:02

Error Input A

RO

0x00 (0dec)

6037:03

Input Status A

RO

0x00 (0dec)

6037:04

Error Input B

RO

0x00 (0dec)

6037:05

Input Status B

RO

0x00 (0dec)

6037:0C

Speed Below Threshold

RO

0x00 (0dec)

6037:10

TxPDO Toggle

RO

0x00 (0dec)

6037:11

Rotational Speed

RO

0x0000 (0dec)

6037:12

Rotation Direction

RO

0x0000 (0dec)

6040:0

Subindex

DI Inputs

RO

0x06 (6dec)

6040:01

Digital Input X4 Pin4

RO

0x00 (0dec)

6040:02

Digital Input X4 Pin2

RO

0x00 (0dec)

6040:03

Digital Input X6 Pin4

RO

0x00 (0dec)

6040:04

Digital Input X6 Pin2

RO

0x00 (0dec)

6040:05

Digital Input X7 Pin4

RO

0x00 (0dec)

6040:06

Digital Input X7 Pin2

RO

0x00 (0dec)

Index (hex)

Name

Flags

Default value

6060:0

Subindex

PWM Inputs

RO

0x12 (18dec)

6060:05

Ready to enable

RO

0x00 (0dec)

6060:06

Warning

RO

0x00 (0dec)

6060:07

Error

RO

0x00 (0dec)

6060:10

TxPDO Toggle

RO

0x00 (0dec)

6060:11

Info data 1

RO

0x0000 (0dec)

6060:12

Info data 2

RO

0x0000 (0dec)

7020:0

Subindex

TACHO Outputs

RO

0x09 (9dec)

7020:09

Reset Error

RO

0x00 (0dec)

7030:0

Subindex

TACHO Outputs

RO

0x09 (9dec)

7030:09

Reset Error

RO

0x00 (0dec)

7050:0

Subindex

DO Outputs

RO

0x06 (6dec)

7050:01

Digital Output X5 Pin4

RO

0x00 (0dec)

7050:02

Digital Output X5 Pin2

RO

0x00 (0dec)

7050:03

Digital Output X6 Pin4

RO

0x00 (0dec)

7050:04

Digital Output X6 Pin2

RO

0x00 (0dec)

7050:05

Digital Output X7 Pin4

RO

0x00 (0dec)

7050:06

Digital Output X7 Pin2

RO

0x00 (0dec)

7060:0

Subindex

PWM Outputs

RO

0x11 (17dec)

7060:01

Enable dithering

RO

0x00 (0dec)

7060:06

Enable

RO

0x00 (0dec)

7060:07

Reset

RO

0x00 (0dec)

7060:11

PWM output

RO

0x0000 (0dec)

7070:0

Subindex

AO Outputs

RO

0x11 (17dec)

7070:11

Analog output

RO

0x0000 (0dec)

8000:0

Subindex

AI Settings Ch.1

RW

0x18 (24dec)

8000:01

Enable user scale

RW

0x00 (0dec)

8000:02

Presentation

RW

0x00 (0dec)

8000:05

Siemens bits

RW

0x00 (0dec)

8000:06

Enable filter

RW

0x00 (0dec)

8000:07

Enable limit 1

RW

0x00 (0dec)

8000:08

Enable limit 2

RW

0x00 (0dec)

8000:0A

Enable user calibration

RW

0x00 (0dec)

8000:0B

Enable vendor calibration

RW

0x01 (1dec)

8000:0E

Swap limit bits

RW

0x00 (0dec)

8000:11

User scale offset

RW

0x0000 (0dec)

8000:12

User scale gain

RW

0x00010000 (65536dec)

8000:13

Limit 1

RW

0x0000 (0dec)

8000:14

Limit 2

RW

0x0000 (0dec)

8000:15

Filter settings

RW

0x0000 (0dec)

8000:17

User calibration offset

RW

0x0000 (0dec)

8000:18

User calibration gain

RW

0x4000 (16384dec)

800E:0

Subindex

AI Internal data Ch.1

RO

0x01 (1dec)

800E:01

ADC raw value

RO

0x0000 (0dec)

Index (hex)

Name

Flags

Default value

800F:0

Subindex

AI Vendor data Ch.1

RW

0x06 (6dec)

800F:01

R0 offset

RW

0x0000 (0dec)

800F:02

R0 gain

RW

0x4000 (16384dec)

800F:03

R1 offset

RW

0x0000 (0dec)

800F:04

R1 gain

RW

0x4000 (16384dec)

800F:05

R2 offset

RW

0x0000 (0dec)

800F:06

R2 gain

RW

0x4000 (16384dec)

8010:0

Subindex

AI Settings Ch.2

RW

0x18 (24dec)

8010:01

Enable user scale

RW

0x00 (0dec)

8010:02

Presentation

RW

0x00 (0dec)

8010:05

Siemens bits

RW

0x00 (0dec)

8010:06

Enable filter

RW

0x00 (0dec)

8010:07

Enable limit 1

RW

0x00 (0dec)

8010:08

Enable limit 2

RW

0x00 (0dec)

8010:0A

Enable user calibration

RW

0x00 (0dec)

8010:0B

Enable vendor calibration

RW

0x01 (1dec)

8010:0E

Swap limit bits

RW

0x00 (0dec)

8010:11

User scale offset

RW

0x0000 (0dec)

8010:12

User scale gain

RW

0x00010000 (65536dec)

8010:13

Limit 1

RW

0x0000 (0dec)

8010:14

Limit 2

RW

0x0000 (0dec)

8010:15

Filter settings

RW

0x0000 (0dec)

8010:17

User calibration offset

RW

0x0000 (0dec)

8010:18

User calibration gain

RW

0x4000 (16384dec)

801E:0

Subindex

AI Internal data Ch.2

RO

0x01 (1dec)

801E:01

ADC raw value

RO

0x0000 (0dec)

801F:0

Subindex

AI Vendor data Ch.2

RW

0x06 (6dec)

801F:01

R0 offset

RW

0x0000 (0dec)

801F:02

R0 gain

RW

0x4000 (16384dec)

801F:03

R1 offset

RW

0x0000 (0dec)

801F:04

R1 gain

RW

0x4000 (16384dec)

801F:05

R2 offset

RW

0x0000 (0dec)

801F:06

R2 gain

RW

0x4000 (16384dec)

8020:0

Subindex

TACHO Settings Dual Shaft Mode Ch.1

RW

0x15 (21dec)

8020:11

No. of Targets

RW

0x0001 (1dec)

8020:12

Input Signal Timeout

RW

0x0064 (100dec)

8020:15

Presentation

RW

0x0001 (1dec)

8030:0

Subindex

TACHO Settings Dual Shaft Mode Ch.2

RW

0x15 (21dec)

8030:11

No. of Targets

RW

0x0001 (1dec)

8030:12

Input Signal Timeout

RW

0x0064 (100dec)

8030:15

Presentation

RW

0x0001 (1dec)

8031:0

Subindex

TACHO Settings Single Shaft Mode

RW

0x15 (21dec)

8031:0B

Enable Error Detection

RW

0x01 (1dec)

8031:0C

Reversion of Rotation

RW

0x00 (0dec)

8031:11

No. of Targets

RW

0x0001 (1dec)

8031:12

Input Signal Timeout

RW

0x0064 (100dec)

8031:15

Presentation

RW

0x0000 (0dec)

Index (hex)

Name

Flags

Default value

8050:0

Subindex

PWM Settings

RW

0x22 (34dec)

8050:03

Enable dithering

RW

0x00 (0dec)

8050:04

Invert polarity

RW

0x00 (0dec)

8050:05

Watchdog

RW

0x00 (0dec)

8050:0B

Offset

RW

0x0000 (0dec)

8050:0C

Gain

RW

0x00010000 (65536dec)

8050:0D

Default output

RW

0x0000 (0dec)

8050:0E

Default output ramp

RW

0xFFFF (65535dec)

8050:10

Max current [%]

RW

0x64 (100dec)

8050:12

Kp factor

RW

0x00FA (250dec)

8050:13

Ki factor

RW

0x0004 (4dec)

8050:14

Kd factor

RW

0x0032 (50dec)

8050:1E

Dithering frequency [Hz]

RW

0x0064 (100dec)

8050:1F

Dithering amplitude [mA]

RW

0x0A (10dec)

8050:21

Select info data 1

RW

0x00 (0dec)

8050:22

Select info data 2

RW

0x00 (0dec)

805F:0

Subindex

PWM Vendor data

RW

0x02 (2dec)

805F:01

Offset

RW

0x0000 (0dec)

805F:02

Gain

RW

0x4000 (16384dec)

8060:0

Subindex

AO Settings

RW

0x16 (22dec)

8060:01

Enable user scale

RW

0x00 (0dec)

8060:02

Presentation

RW

0x00 (0dec)

8060:05

Watchdog

RW

0x00 (0dec)

8060:07

Enable user calibration

RW

0x00 (0dec)

8060:08

Enable vendor calibration

RW

0x01 (1dec)

8060:11

User scale offset

RW

0x0000 (0dec)

8060:12

User scale gain

RW

0x00010000 (65536dec)

8060:13

Default output

RW

0x0000 (0dec)

8060:14

Default output ramp

RW

0xFFFF (65535dec)

8060:15

User calibration offset

RW

0x0000 (0dec)

8060:16

User calibration gain

RW

0x4000 (16384dec)

806E:0

Subindex

AO Internal data

RO

0x01 (1dec)

806E:01

DAC raw value

RO

0x0000 (0dec)

806F:0

Subindex

AO Vendor data

RW

0x06 (6dec)

806F:01

R0 Calibration Offset

RW

0x0000 (0dec)

806F:02

R0 Calibration Gain

RW

0x4000 (16384dec)

806F:03

R1 Calibration Offset

RW

0x0000 (0dec)

806F:04

R1 Calibration Gain

RW

0x4000 (16384dec)

806F:05

R2 Calibration Offset

RW

0x0000 (0dec)

806F:06

R2 Calibration Gain

RW

0x4000 (16384dec)

A060:0

Subindex

PWM Diag data

RO

0x06 (6dec)

A060:02

Overtemperature

RO

0x00 (0dec)

060A:06

Short circuit

RO

0x00 (0dec)

F000:0

Subindex

Modular device profile

RO

0x02 (2dec)

F000:01

Module index distance

RO

0x0010 (16dec)

F000:02

Maximum number of modules

RO

0x0008 (8dec)

Index (hex)

Name

Flags

Default value

F008

Code word

RW

0x00000000 (0dec)

F010:0

Subindex

Module list

RW

0x08 (8dec)

F010:01

SubIndex 001

RW

0x0000012C (300dec)

F010:02

SubIndex 002

RW

0x0000012C (300dec)

F010:03

SubIndex 003

RW

0x00000208 (520dec)

F010:04

SubIndex 004

RW

0x00000208 (520dec)

F010:05

SubIndex 005

RW

0x00000064 (100dec)

F010:06

SubIndex 006

RW

0x000000C8 (200dec)

F010:07

SubIndex 007

RW

0x000000FA (250dec)

F010:08

SubIndex 008

RW

0x00000190 (400dec)

F800:0

Subindex

AIAO Range settings

RW

0x08 (8dec)

800F:01

Input type Ch1

RW

0x0001 (1dec)

800F:02

Input type Ch2

RW

0x0001 (1dec)

800F:08

Output type

RW

0x0001 (1dec)

F900:0

Subindex

PWM Info data

RO

0x02 (2dec)

F900:02

Temperature [°C]

RO

0x00 (0dec)

FB00:0

Subindex

PWM Command

RO

0x03 (3dec)

FB00:01

Request

RW

{0}

FB00:02

Status

RO

0x00 (0dec)

FB00:03

Response

RO

{0}

Legend

Flags:
RO (Read Only): this object can only be read
RW (Read/Write): this object can be read and written to