Status LEDs

Status LEDs 1:
Status LEDs at the M12 connections

Status LEDs at M12 connections 1 and 2 (inputs)

Connection

LED

Display

Meaning

M12 socket no. 1 and 2

R
left

off

No data transfer to the D/A converter

green

Data transfer to the D/A converter

E
right

off

Function OK

red

Error: Open circuit or measured value outside of the measuring range (smaller than 3.5 mA/-11 V or larger than 21 mA/11 V)

Correct function is indicated if the green Run LED is on and the red Error LED is off.

Status LEDs at M12 connections 3 and 4 (outputs)

Connection

LED

Display

Meaning

M12 socket no. 3 and 4

R
left

off

No data transfer to the D/A converter

green

Data transfer to the D/A converter