Configuration data

Index 80n0 AI settings (for n = 0: channel 1; n = 1: channel 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

AI Settings

Maximum subindex

UINT8

RO

0x20 (32dec)

80n0:07

Enable limit

Activate limit evaluation (deviates from other EL terminals!)

BOOLEAN

RW

0x0 (FALSE)

80n0:0A

Enable user calibration

Enabling of the user calibration

BOOLEAN

RW

0x0 (FALSE

80n0:0B

Enable vendor calibration

Enabling of the vendor calibration

BOOLEAN

RW

0x1 (TRUE)

80n0:13

Limit 1

Upper limit value

INT16

RW

0x0000 (0dec)

80n0:14

Limit 2

Lower limit value

INT16

RW

0x0000 (0dec)

80n0:15

Filter settings

Filter settings

0: 10 Hz, Gain 20
1: 100 Hz
2: 500 Hz
3: 1000 Hz
4: 5000 Hz
5: 10000 Hz
6: 25000 Hz
7: 2000 Hz (from firmware 11)

ENUM

RW

10000 Hz (5)

80n0:17

User calibration offset

User calibration offset

INT16

RW

0

80n0:18

User calibration gain

User calibration gain factor

INT16

RW

16384

80n0:20

Supply current

Sensor current setting
0: 2 mA
1: 4 mA
2: 8 mA

ENUM

RW

2 mA (0)

80n0:21

Active offset adjustment

Automatic offset calculation
0: Disabled
1: Level 1
2: Level 2
3: Level 3
4: Level 4
5: Level 5
6: Level 6
7: Level 7
8: Level 8

ENUM

RW

Disabled (0)

Index 80n8 AI advanced settings (for n = 0: channel 1; n = 1: channel 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

80n8:0

AI Advanced Settings

Maximum subindex

UINT8

RO

0x06 (6dec)

80n8:06

Input Amplifier

permitted values:

BIT2

RW

0x00 (0dec)

0: Preset (setting via object 0x80n0:15)

1: ON (switch-on of the analog amplifier x20 irrespective of filter settings; gain factor of 20 is not changeable)

2: OFF (switch-off of the analog amplifier irrespective of the filter settings)

Index 8012 AI Device settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8012:0

AI Device Settings

Maximum subindex

UINT8

RO

0x11 (17dec)

8012:11

DC Timestamp Shift

 

UINT32

RW

0x00000000 (0dec)

Index 80nF AI Vendor data (for n = 0: channel 1; n = 1: channel 2)

Index (hex)

Name

Meaning

Data type

Flags

Default

80nF:0

AI vendor data

Maximum subindex

UINT8

RO

0x04 (4dec)

80nF:01

Calibration offset (gain 1)

Offset (vendor calibration), gain 1

INT16

RW

0x0000 (0dec)

80nF:02

Calibration gain (gain 1)

Gain (vendor calibration), gain 1

INT16

RW

0x0000 (0dec)

80nF:03

Calibration offset (gain 20)

Offset (vendor calibration), gain 20

INT16

RW

0x0000 (0dec)

80nF:04

Calibration gain (gain 20)

Gain (vendor calibration), gain 20

INT16

RW

0x0000 (0dec)