Profile-specific objects (0x6000-0xFFFF)

The profile-specific objects have the same meaning for all EtherCAT slaves that support the profile 5001.

Index 6000: TC Inputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6000:0

TC Inputs Ch.1

Maximum subindex

UINT8

RO

0x11 (17dec)

6000:01

Underrange

Is set if the value falls below the operating range of the sensor or the process record contains the lowest possible value.

BOOLEAN

RO

0x00 (0dec)

6000:02

Overrange

Is set if the value exceeds the operating range of the sensor or the process record contains the highest possible value.

BOOLEAN

RO

0x00 (0dec)

6000:03

Limit 1

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6000:05

Limit 2

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6000:07

Error

The error bit is set if the process data is invalid (cable break, overrange, underrange)

BOOLEAN

RO

0x00 (0dec)

6000:0E

Sync error

Only in DC: bit is set if the slave is not able to operate synchronous with master, because it cannot keep up with the cycle time.

BOOLEAN

RO

0x00 (0dec)

6000:0F

TxPDO State

Validity of the data of the associated TxPDO

BOOLEAN

RO

0x00 (0dec)

0

valid

1

invalid

6000:10

TxPDO Toggle

TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

6000:11

Value

Analog input value (resolution in 1/10 °C)

INT16

RO

0x0000 (0dec)

Index 6010: TC Inputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

6010:0

TC Inputs Ch.2

Maximum subindex

UINT8

RO

0x11 (17dec)

6010:01

Underrange

Is set if the value falls below the operating range of the sensor or the process record contains the lowest possible value.

BOOLEAN

RO

0x00 (0dec)

6010:02

Overrange

Is set if the value exceeds the operating range of the sensor or the process record contains the highest possible value.

BOOLEAN

RO

0x00 (0dec)

6010:03

Limit 1

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6010:05

Limit 2

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6010:07

Error

The error bit is set if the process data is invalid (cable break, overrange, underrange)

BOOLEAN

RO

0x00 (0dec)

6010:0E

Sync error

Only in DC: bit is set if the slave is not able to operate synchronous with master, because it cannot keep up with the cycle time.

BOOLEAN

RO

0x00 (0dec)

6010:0F

TxPDO State

Validity of the data of the associated TxPDO

BOOLEAN

RO

0x00 (0dec)

0

valid

1

invalid

6010:10

TxPDO Toggle

TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

6010:11

Value

Analog input value (resolution in 1/10 °C)

INT16

RO

0x0000 (0dec)

Index 6020: TC Inputs Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

6020:0

TC Inputs Ch.3

Maximum subindex

UINT8

RO

0x11 (17dec)

6020:01

Underrange

Is set if the value falls below the operating range of the sensor or the process record contains the lowest possible value.

BOOLEAN

RO

0x00 (0dec)

6020:02

Overrange

Is set if the value exceeds the operating range of the sensor or the process record contains the highest possible value.

BOOLEAN

RO

0x00 (0dec)

6020:03

Limit 1

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2


Set limit exceeded

3


Set limit reached

6020:05

Limit 2

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2


Set limit exceeded

3


Set limit reached

6020:07

Error

The error bit is set if the process data is invalid (cable break, overrange, underrange)

BOOLEAN

RO

0x00 (0dec)

6020:0E

Sync error

Only in DC: bit is set if the slave is not able to operate synchronous with master, because it cannot keep up with the cycle time.

BOOLEAN

RO

0x00 (0dec)

6020:0F

TxPDO State

Validity of the data of the associated TxPDO

BOOLEAN

RO

0x00 (0dec)

0

valid

1

invalid

6020:10

TxPDO Toggle

TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

6020:11

Value

Analog input value (resolution in 1/10°C)

INT16

RO

0x0000 (0dec)

Index 6030: TC Inputs Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

6030:0

TC Inputs Ch.4

Maximum subindex

UINT8

RO

0x11 (17dec)

6030:01

Underrange

Is set if the value falls below the operating range of the sensor or the process record contains the lowest possible value.

BOOLEAN

RO

0x00 (0dec)

6030:02

Overrange

Is set if the value exceeds the operating range of the sensor or the process record contains the highest possible value.

BOOLEAN

RO

0x00 (0dec)

6030:03

Limit 1

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit reached

3

Set limit exceeded

6030:05

Limit 2

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit reached

3

Set limit exceeded

6030:07

Error

The error bit is set if the process data is invalid (cable break, overrange, underrange)

BOOLEAN

RO

0x00 (0dec)

6030:0E

Sync error

Only in DC: bit is set if the slave is not able to operate synchronous with master, because it cannot keep up with the cycle time.

BOOLEAN

RO

0x00 (0dec)

6030:0F

TxPDO State

Validity of the data of the associated TxPDO

BOOLEAN

RO

0x00 (0dec)

0

valid

1

invalid

6030:10

TxPDO Toggle

TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

6030:11

Value

Analog input value (resolution in 1/10°C)

INT16

RO

0x0000 (0dec)

Index 7000: TC Outputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

7000:0

TC Outputs Ch.1

Maximum subindex

UINT8

RO

0x11 (17dec)

7000:11

CJCompensation

Temperature of the cold junction (resolution in 1/10°C)
(index 0x8000:0C, comparison via the process data))

INT16

RO

0x0000 (0dec)

Index 7010: TC Outputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

7010:0

TC Outputs Ch.2

Maximum subindex

UINT8

RO

0x11 (17dec)

7010:11

CJCompensation

Temperature of the cold junction (resolution in 1/10°C)
(index 0x8000:0C, comparison via the process data)

INT16

RO

0x0000 (0dec)

Index 7020: TC Outputs Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

7020:0

TC Outputs Ch.3

Maximum subindex

UINT8

RO

0x11 (17dec)

7020:11

CJCompensation

Temperature of the cold junction (resolution in 1/10°C)
(index 0x8020:0C, comparison via the process data)

INT16

RO

0x0000 (0dec)

Index 7030: TC Outputs Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

7030:0

TC Outputs Ch.4

Maximum subindex

UINT8

RO

0x11 (17dec)

7030:11

CJCompensation

Temperature of the cold junction (resolution in 1/10°C)
(index 0x8030:0C, comparison via the process data)

INT16

RO

0x0000 (0dec)

Index 800E: TC Internal data Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

800E:0

TC Internal data Ch.1

Maximum subindex

UINT8

RO

0x05 (5dec)

800E:01

ADC raw value TC

Raw value of the analog/digital converter for the thermocouple

INT32

RO

0x00000000 (0dec)

800E:02

ADC raw value PT1000

Raw value of the analog/digital converter for the Pt1000

INT32

RO

0x00000000 (0dec)

800E:03

CJ temperature

Cold junction temperature (resolution 1/100 °C)

INT16

RO

0x0000 (0dec)

800E:04

CJ voltage

Cold junction voltage (resolution 1 µV)

INT16

RO

0x0000 (0dec)

800E:05

CJ resistor

Cold junction resistance for Pt1000 temperature sensor (resolution 1/10 ohm)

UINT16

RO

0x0000 (0dec)

Index 800F: TC Vendor data Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

800F:0

TC Vendor data Ch.1

Maximum subindex

UINT8

RO

0x04 (4dec)

800F:01

Calibration offset TC

Manufacturer calibration for thermocouple: Offset

INT16

RW

0x0000 (0dec)

800F:02

Calibration gain TC

Manufacturer calibration for thermocouple: Gain

UINT16

RW

0x4000 (16384dec)

800F:03

Calibration offset CJ

Manufacturer calibration for cold junction (Pt1000): Offset

INT16

RW

0x0000 (0dec)

800F:04

Calibration gain CJ

Manufacturer calibration for cold junction (Pt1000): Gain

UINT16

RW

0x4000 (16384dec)

Index 801E: TC Internal data Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

801E:0

TC Internal data Ch.2

Maximum subindex

UINT8

RO

0x05 (5dec)

801E:01

ADC raw value TC

Raw value of the analog/digital converter for the thermocouple

INT32

RO

0x00000000 (0dec)

801E:02

ADC raw value PT1000

Raw value of the analog/digital converter for the Pt1000

INT32

RO

0x00000000 (0dec)

801E:03

CJ temperature

Cold junction temperature (resolution 1/100 °C)

INT16

RO

0x0000 (0dec)

801E:04

CJ voltage

Cold junction voltage (resolution 1 µV)

INT16

RO

0x0000 (0dec)

801E:05

CJ resistor

Cold junction resistance for Pt1000 temperature sensor (resolution 1/10 ohm)

UINT16

RO

0x0000 (0dec)

Index 801F: TC Vendor data Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

801F:0

TC Vendor data Ch.2

Maximum subindex

UINT8

RO

0x04 (4dec)

801F:01

Calibration offset TC

Manufacturer calibration for thermocouple: Offset

INT16

RW

0x0000 (0dec)

801F:02

Calibration gain TC

Manufacturer calibration for thermocouple: Gain

UINT16

RW

0x4000 (16384dec)

801F:03

Calibration offset CJ

Manufacturer calibration for cold junction (Pt1000): Offset

INT16

RW

0x0000 (0dec)

801F:04

Calibration gain CJ

Manufacturer calibration for cold junction (Pt1000): Gain

UINT16

RW

0x4000 (16384dec)

Index 802E: TC Internal data Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

802E:0

TC Internal data Ch.3

Maximum subindex

UINT8

RO

0x05 (5dec)

802E:01

ADC raw value TC

Raw value of the analog/digital converter for the thermocouple

INT32

RO

0x00000000 (0dec)

802E:02

ADC raw value PT1000

Raw value of the analog/digital converter for the Pt1000

INT32

RO

0x00000000 (0dec)

802E:03

CJ temperature

Cold junction temperature (resolution 1/100 °C)

INT16

RO

0x0000 (0dec)

802E:04

CJ voltage

Cold junction voltage (resolution 1 µV)

INT16

RO

0x0000 (0dec)

802E:05

CJ resistor

Cold junction resistance for Pt1000 temperature sensor (resolution 1/10 ohm)

UINT16

RO

0x0000 (0dec)

Index 802F: TC Vendor data Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

802F:0

TC Vendor data Ch.3

Maximum subindex

UINT8

RO

0x04 (4dec)

802F:01

Calibration offset TC

Manufacturer calibration for thermocouple: Offset

INT16

RW

0x0000 (0dec)

802F:02

Calibration gain TC

Manufacturer calibration for thermocouple: Gain

UINT16

RW

0x4000 (16384dec)

802F:03

Calibration offset CJ

Manufacturer calibration for cold junction (Pt1000): Offset

INT16

RW

0x0000 (0dec)

802F:04

Calibration gain CJ

Manufacturer calibration for cold junction (Pt1000): Gain

UINT16

RW

0x4000 (16384dec)

Index 803E: TC Internal data Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

803E:0

TC Internal data Ch.4

Maximum subindex

UINT8

RO

0x05 (5dec)

803E:01

ADC raw value TC

Raw value of the analog/digital converter for the thermocouple

INT32

RO

0x00000000 (0dec)

803E:02

ADC raw value PT1000

Raw value of the analog/digital converter for the Pt1000

INT32

RO

0x00000000 (0dec)

803E:03

CJ temperature

Cold junction temperature (resolution 1/100 °C)

INT16

RO

0x0000 (0dec)

803E:04

CJ voltage

Cold junction voltage (resolution 1 µV)

INT16

RO

0x0000 (0dec)

803E:05

CJ resistor

Cold junction resistance for Pt1000 temperature sensor (resolution 1/10 ohm)

UINT16

RO

0x0000 (0dec)

Index 803F: TC Vendor data Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

803F:0

TC Vendor data Ch.4

Maximum subindex

UINT8

RO

0x04 (4dec)

803F:01

Calibration offset TC

Manufacturer calibration for thermocouple: Offset

INT16

RW

0x0000 (0dec)

803F:02

Calibration gain TC

Manufacturer calibration for thermocouple: Gain

UINT16

RW

0x4000 (16384dec)

803F:03

Calibration offset CJ

Manufacturer calibration for cold junction (Pt1000): Offset

INT16

RW

0x0000 (0dec)

803F:04

Calibration gain CJ

Manufacturer calibration for cold junction (Pt1000): Gain

UINT16

RW

0x4000 (16384dec)

Index F000: Modular device profile

Index (hex)

Name

Meaning

Data type

Flags

Default

F000:0

Modular device profile

Maximum subindex

UINT8

RO

0x02 (2dec)

F000:01

Module index distance

Index spacing for the objects of the individual channels

UINT16

RO

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RO

0x0004 (4dec)

Index F008: Code word

Index (hex)

Name

Meaning

Data type

Flags

Default

F008:0

Code word

reserved

UINT32

RW

0x00000000 (0dec)

Index F010: Module list

Index (hex)

Name

Meaning

Data type

Flags

Default

F010:0

Module list

Maximum subindex

UINT8

RW

0x04 (4dec)

F010:01

SubIndex 001

 

UINT32

RW

0x0000014A (330dec)

F010:02

SubIndex 002

 

UINT32

RW

0x0000014A (330dec)

F010:03

SubIndex 003

 

UINT32

RW

0x0000014A (330dec)

F010:04

SubIndex 004

 

UINT32

RW

0x0000014A (330dec)

Index F080: Channel Enable

Index (hex)

Name

Meaning

Data type

Flags

Default

F080:0

Channel Enable

Maximum subindex

UINT8

RO

0x04 (4dec)

F080:01

SubIndex 001

0

Channel 1 disabled

(from hardware version 01 deactivated channels are not measured, and the green LED R for these channels goes out)

BOOLEAN

RW

0x01 (1dec)

1

Channel 1 enabled

F080:02

SubIndex 002

0

Channel 2 disabled

BOOLEAN

RW

0x01 (1dec)

1

Channel 2 enabled

F080:03

SubIndex 003

0

Channel 3 disabled

BOOLEAN

RW

0x01 (1dec)

1

Channel 3 enabled

F080:04

SubIndex 004

0

Channel 4 disabled

BOOLEAN

RW

0x01 (1dec)

1

Channel 5 enabled