Standard objects (0x1000-0x1FFF)

The standard objects have the same meaning for all EtherCAT slaves.

Index 1000: Device type

Index (hex)

Name

Meaning

Data type

Flags

Default

1000:0

Device type

Device type of the EtherCAT slave: The Low-Word contains the CoE profile used (5001). The High-Word contains the module profile according to the modular device profile.

UINT32

RO

0x01401389 (20976521dec)

Index 1008: Device name

Index (hex)

Name

Meaning

Data type

Flags

Default

1008:0

Device name

Device name of the EtherCAT slave

STRING

RO

EP3204-0002

Index 1009: Hardware version

Index (hex)

Name

Meaning

Data type

Flags

Default

1009:0

Hardware version

Hardware version of the EtherCAT slave

STRING

RO

05

Index 100A: Software version

Index (hex)

Name

Meaning

Data type

Flags

Default

100A:0

Software version

Firmware version of the EtherCAT slave

STRING

RO

07

Index 1018: Identity

Index (hex)

Name

Meaning

Data type

Flags

Default

1018:0

Identity

Information for identifying the slave

UINT8

RO

0x04 (4dec)

1018:01

Vendor ID

Vendor ID of the EtherCAT slave

UINT32

RO

0x00000002 (2dec)

1018:02

Product code

Product code of the EtherCAT slave

UINT32

RO

0x0C844052 (209993810dec)

1018:03

Revision

Revision number of the EtherCAT slave; the low word (bit 0-15) indicates the special terminal number, the high word (bit 16-31) refers to the device description

UINT32

RO

0x00120002 (1179650dec)

1018:04

Serial number

Serial number of the EtherCAT slave; the low byte (bit 0-7) of the low word contains the year of production, the high byte (bit 8-15) of the low word contains the week of production, the high word (bit 16-31) is 0

UINT32

RO

0x00000000 (0dec)

Index 10F0: Backup parameter handling

Index (hex)

Name

Meaning

Data type

Flags

Default

10F0:0

Backup parameter handling

Information for standardized loading and saving of backup entries

UINT8

RO

0x01 (1dec)

10F0:01

Checksum

Checksum across all backup entries of the EtherCAT slave

UINT32

RO

0x00000000 (0dec)

Index 1A00: RTD TxPDO-Map RTDInputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

1A00:0

RTD TxPDO-Map RTDInputs Ch.1

PDO Mapping TxPDO 1

UINT8

RO

0x09 (9dez)

1A00:01

SubIndex 001

1. PDO Mapping entry

UINT32

RO

0x6000:01, 1

1A00:02

SubIndex 002

2. PDO Mapping entry

UINT32

RO

0x6000:02, 1

1A00:03

SubIndex 003

3. PDO Mapping entry

UINT32

RO

0x6000:03, 2

1A00:04

SubIndex 004

4. PDO Mapping entry

UINT32

RO

0x6000:05, 2

1A00:05

SubIndex 005

5. PDO Mapping entry

UINT32

RO

0x6000:07, 1

1A00:06

SubIndex 006

6. PDO Mapping entry (7 bits align)

UINT32

RO

0x0000:00, 7

1A00:07

SubIndex 007

7. PDO Mapping entry

UINT32

RO

0x6000:0, 1

1A00:08

SubIndex 008

8. PDO Mapping entry

UINT32

RO

0x6000:10, 1

1A00:09

SubIndex 009

9. PDO Mapping entry

UINT32

RO

0x6000:11, 16

Index 1A01: RTD TxPDO-Map RTDInputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

1A01:0

RTD TxPDO-Map RTDInputs Ch.2

PDO Mapping TxPDO 2

UINT8

RO

0x09 (9dez)

1A01:01

SubIndex 001

1. PDO Mapping entry

UINT32

RO

0x6010:01, 1

1A01:02

SubIndex 002

2. PDO Mapping entry

UINT32

RO

0x6010:02, 1

1A01:03

SubIndex 003

3. PDO Mapping entry

UINT32

RO

0x6010:03, 2

1A01:04

SubIndex 004

4. PDO Mapping entry

UINT32

RO

0x6010:05, 2

1A01:05

SubIndex 005

5. PDO Mapping entry

UINT32

RO

0x6010:07, 1

1A01:06

SubIndex 006

6. PDO Mapping entry (7 bits align)

UINT32

RO

0x0000:00, 7

1A01:07

SubIndex 007

7. PDO Mapping entry

UINT32

RO

0x6010:0F, 1

1A01:08

SubIndex 008

8. PDO Mapping entry

UINT32

RO

0x6010:10, 1

1A01:09

SubIndex 009

9. PDO Mapping entry

UINT32

RO

0x6010:11, 16

Index 1A02: RTD TxPDO-Map RTDInputs Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

1A02:0

RTD TxPDO-Map RTDInputs Ch.3

PDO Mapping TxPDO 3

UINT8

RO

0x09 (9dez)

1A02:01

SubIndex 001

1. PDO Mapping entry

UINT32

RO

0x6020:01, 1

1A02:02

SubIndex 002

2. PDO Mapping entry

UINT32

RO

0x6020:02, 1

1A02:03

SubIndex 003

3. PDO Mapping entry

UINT32

RO

0x6020:03, 2

1A02:04

SubIndex 004

4. PDO Mapping entry

UINT32

RO

0x6020:05, 2

1A02:05

SubIndex 005

5. PDO Mapping entry

UINT32

RO

0x6020:07, 1

1A02:06

SubIndex 006

6. PDO Mapping entry (7 bits align)

UINT32

RO

0x0000:00, 7

1A02:07

SubIndex 007

7. PDO Mapping entry

UINT32

RO

0x6020:0F, 1

1A02:08

SubIndex 008

8. PDO Mapping entry

UINT32

RO

0x6020:10, 1

1A02:09

SubIndex 009

9. PDO Mapping entry

UINT32

RO

0x6020:11, 16

Index 1A03: RTD TxPDO-Map RTDInputs Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

1A03:0

RTD TxPDO-Map RTDInputs Ch.4

PDO Mapping TxPDO 4

UINT8

RO

0x09 (9dez)

1A03:01

SubIndex 001

1. PDO Mapping entry

UINT32

RO

0x6030:01, 1

1A03:02

SubIndex 002

2. PDO Mapping entry

UINT32

RO

0x6030:02, 1

1A03:03

SubIndex 003

3. PDO Mapping entry

UINT32

RO

0x6030:03, 2

1A03:04

SubIndex 004

4. PDO Mapping entry

UINT32

RO

0x6030:05, 2

1A03:05

SubIndex 005

5. PDO Mapping entry

UINT32

RO

0x6030:07, 1

1A03:06

SubIndex 006

6. PDO Mapping entry (7 bits align)

UINT32

RO

0x0000:00, 7

1A03:07

SubIndex 007

7. PDO Mapping entry

UINT32

RO

0x6030:0F, 1

1A03:08

SubIndex 008

8. PDO Mapping entry

UINT32

RO

0x6030:10, 1

1A03:09

SubIndex 009

9. PDO Mapping entry

UINT32

RO

0x6030:11, 16

Index 1C00: Sync manager type

Index (hex)

Name

Meaning

Data type

Flags

Default

1C00:0

Sync manager type

Using the sync managers

UINT8

RO

0x04 (4dec)

1C00:01

SubIndex 001

Sync-Manager Type Channel 1: Mailbox Write

UINT8

RO

0x01 (1dec)

1C00:02

SubIndex 002

Sync-Manager Type Channel 2: Mailbox Read

UINT8

RO

0x02 (2dec)

1C00:03

SubIndex 003

Sync-Manager Type Channel 3: Process Data Write (Outputs)

UINT8

RO

0x03 (3dec)

1C00:04

SubIndex 004

Sync-Manager Type Channel 4: Process Data Read (Inputs)

UINT8

RO

0x04 (4dec)

Index 1C12: RxPDO assign

Index (hex)

Name

Meaning

Data type

Flags

Default

1C12:0

RxPDO assign

PDO Assign Outputs

UINT8

RW

0x00 (0dec)

Index 1C13: TxPDO assign

Index (hex)

Name

Meaning

Data type

Flags

Default

1C13:0

TxPDO assign

PDO Assign Inputs

UINT8

RW

0x04 (4dec)

1C13:01

Subindex 001

1. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A00 (6656dec)

1C13:02

Subindex 002

2. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A01 (6657dec)

1C13:03

Subindex 003

3. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A02 (6658dec)

1C13:04

Subindex 004

4. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A03 (6659dec)

Index 1C33: SM input parameter

Index (hex)

Name

Meaning

Data type

Flags

Default

1C33:0

SM input parameter

Maximum subindex

UINT8

RO

0x20 (32dec)

1C33:01

Sync mode

 

UINT16

RW

0x0000 (0dec)

1C33:02

Cycle time

 

UINT32

RW

0x000F4240 (1000000dec)

1C33:03

Shift time

 

UINT32

RO

0x00000000 (0dec)

1C33:04

Sync modes supported

 

UINT16

RO

0xC007 (49159dec)

1C33:05

Minimum cycle time

 

UINT32

RO

0x00002710 (10000dec)

1C33:06

Calc and copy time

 

UINT32

RO

0x00000000 (0dec)

1C33:07

Minimum delay time

 

UINT32

RO

0x00000000 (0dec)

1C33:08

Command

 

UINT16

RW

0x0000 (0dec)

1C33:09

Maximum Delay time

 

UINT32

RO

0x00000000 (0dec)

1C33:0B

SM event missed counter

 

UINT16

RO

0x0000 (0dec)

1C33:0C

Cycle exceeded counter

 

UINT16

RO

0x0000 (0dec)

1C33:0D

Shift too short counter

 

UINT16

RO

0x0000 (0dec)

1C33:20

Sync error

 

BOOLEAN

RO

0x00 (0dec)