Enable additional diagnostic functions

The following products allow advanced diagnostics of their digital outputs:

The following diagnostic functions are disabled in the factory setting of these products:

You can enable these diagnostic functions for each digital output channel individually. Example for channel 1:

Enable additional diagnostic functions 1:

Function

CoE parameters to enable

Wire break detection with output switched off

80n00:01

Detect open wire in off state

Wire break detection with output switched on

80n00:02

Detect open wire in on state

Detection of short circuits after 24 V

80n00:03

Detect short to 24V