Technical data - EK3100

Technical data

EK3100

Bus interface

1 x D-sub socket, 9-pin with shielding

Protocol

PROFIBUS DP

Data transfer rates

up to max. 12 Mbit/s (automatic recognition)

Interfaces

1 x USB (behind the front flap)

Web interface

yes

Power supply

24 V DC (-15 %/+20 %)

Power contacts

24 V DC max./10 A max.

Electrical isolation

500 V (power contact/supply voltage)

Max. power loss

3 W

I/O connection

E-bus (EtherCAT Terminals)

Power supply for I/O terminals

max. 2 A

I/O terminals

E-bus (EL, ES, EP), standard digital signals, standard analog signals. All compatible EtherCAT devices are listed in the GSD file.
No gateway EC terminals, no EC terminals with XFC or DC function.

Number of EtherCAT devices

max. 255

Dimensions (W x H x L)

65 mm x 100 mm x 73 mm

Weight

approx. 215 g

Operating/storage temperature
horizontal mounting position

-25°C … +60°C/-40°C … +85°C
see note! **)

Operating/storage temperature
other mounting position

0…+55 °C/-25…+85 °C
see note! **)

Relative humidity

95 % no condensation

Vibration/shock resistance

Conforms to EN 60068-2-6/EN 60068-2-27

EMC immunity/emission

Conforms to EN 61000-6-2/EN 61000-6-4

Protect. class / installation pos.

IP 20/variable

Markings / Approvals*)

CE, EAC, UKCA
cULus, IECEx, ATEX

*) Real applicable approvals/markings see type plate on the side (product marking).

Technical data - EK3100 1:

E-Bus current/mounting positions **)

- for -25°C..+60°C only horizontal mounting position, E-bus current 1 A max.
- for 0...+55°C mounting position any, E-bus current 2 A max.

Ex markings

Standard

Marking

ATEX

II 3 G Ex nA IIC T4 Gc

IECEx

Ex nA IIC T4 Gc