Technical data - PROFIBUS

Technical data

PROFIBUS (EK3100)

Number of I/O modules

depending on controller

Number of I/O points

depending on controller

Data transfer medium

shielded copper cable, 2 x 0.25 mm²

Cable length 

1200 m

1000 m

400 m

200 m

100 m

Data transfer rate

9.6/19.2/93.75 kbit/s

187.5 kbit/s

500 kbit/s

1500 kbit/s

3 /6 /12 Mbit/s

Topology

Line topology

Fieldbus

PROFIBUS DP

Bus interface

1 x D sub-socket, 9-pin

Extendable process image

Up to 3 virtual slaves in addition

max. process image

4 slaves x (240 bytes in / 240 bytes out)

Protocol

 

PROFIBUS DP slave

Yes

PROFIBUS-DP (virtual slave)

4 (3 virtual PROFIBUS nodes)

Functions/Services

 

PROFIBUS

DP

DPV1 class 1

Yes

Diagnostics/Status/Alarm

 

RUN LED

Yes, green/red

BF LED

Yes, green/red

DIA LED

Yes, green/red