EK1501, EK1501-0010, EK1541

EK1501, EK1501-0010, EK1541 1:
Diagnostic LEDs for Bus Coupler EK15x1-00x0

LEDs for power supply diagnostics

LED

Display

State

Description

Us

green

off

-

No operating voltage present at the Bus Coupler

on

-

24 VDC operating voltage present at the Bus Coupler

Up

green

off

-

No power supply present at the power contacts

on

-

24 VDC power supply present at the power contacts

Diagnostic LEDs for the EtherCAT State Machine/PLC

LED

Display

State

Description

RUN

green

off

Init

The Bus Coupler is in initialization state

flashing

Pre-Operational

The Bus Coupler is in pre-operational state

single flash

Safe-Operational

The Bus Coupler is in safe-operational state

on

Operational

The Bus Coupler is in operational state

flickers

Bootstrap

Firmware is being loaded.

LEDs for fieldbus diagnostics

LED

Display

State

Description

LINK / ACT
(X1 IN)

green

off

-

No connection on the incoming EtherCAT segment

on

linked

Preceding EtherCAT device connected

flashes

active

Communication with preceding EtherCAT device

LINK / ACT
(X2 OUT)

green

off

-

No connection on the outgoing EtherCAT segment

on

linked

Following EtherCAT device connected

flashes

active

Communication with following EtherCAT device

LINK / ACT  E‑bus

green

off

-

no connection to internal E-bus

on

linked

Connection to internal E-bus

flashes

active

Connection/communication internal E-bus