Diagnostic LEDs

Diagnostic LEDs 1:
EK1000 LEDs

Ethernet interface X001

LED

Display

State

Description

LINK / ACT
(X001 IN)

green

off

-

Link not available/no activity

on

linked

Link available/activity

LED power supply terminal

Diagnostic LEDs 2:
Diagnostic LEDs

LED

Display

State

Description

Us

green

off

-

No operating voltage present at the Bus Coupler

on

-

24 VDC operating voltage present at the Bus Coupler

Up

green

off

-

No power supply present at the power contacts

on

-

24 VDC power supply present at the power contacts

LINK / ACT
(X002 OUT)

green

off

-

No EtherCAT device connected

on

linked

EtherCAT device connected / data communication not active

flashes

active

EtherCAT device connected / data communication active

LED coupler

LED

Display

State

Description

RUN

green

on

-

Coupler is ready

EC

green

off

Init

The Bus Coupler is in initialization state

flashes

Pre-Operational

The Bus Coupler is in pre-operational state

Single flash

Safe-Operational

The Bus Coupler is in safe-operational state

on

Operational

The Bus Coupler is in operational state

flickering

Bootstrap

Firmware is being loaded.

ERR

red

off

-

No error

flashes at 2 Hz

-

Used to visually locate the corresponding device. Triggered by "Start Signal" function in the Broadcast Search

on

-

Error is signaled