EJ9400 - Power supply plug-in module for E-bus, 2.5 A

EJ9400 - Technical data

 
 
 
 
 
Technical data
EJ9400
Short-circuit-proof
-
Input voltage
24 VDC (-15 % / +20 %)
Input current
0.41 A (0.43 A / 0.57 A )
Max. output current
2.5 A
Current consumption via E-bus
-
Electrical isolation
-
Diagnostics in the process image
-
permissible ambient temperature range during operation
-25°C .. + 60°C (extended temperature range from Hardware 02)
permissible ambient temperature range during storage
-40°C .. + 60°C
permissible relative humidity
95 %, no condensation
Operating altitude
max. 2,000 m
Dimensions (W x H x D)
approx. 12 mm x 66 mm x 55 mm
Weight
approx. 30 g
Mounting
on signal distribution board
Pollution degree
2
Installation position
7 and 8
Color coding
grey
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27 (with corresponding signal distribution board)
EMC immunity/emission
conforms to EN 61000-6-2/EN 61000-6-4 (with corresponding signal distribution board)
Protection class
EJ module: IP20,
EJ system: dependent on signal distribution board and housing
Approval
CE, UL
 
 
CE approval
The CE Marking refers to the EtherCAT plug-in module mentioned above.
If the EtherCAT plug-in module is used in the production of a ready-to-use end product (PCB in conjunction with a housing), the manufacturer of the end product must check compliance of the overall system with relevant directives and CE certification.
To operate the EtherCAT plug-in modules, they must be installed in a housing.