PDO Assignment

The scope of the process data offered varies depending on the configured IO-Link ports.
“DeviceState Inputs Device” and “DeviceState Inputs” are selected by default. Device-specific PDOs (0x1A0n “Port (n-1) Process Data”) are only displayed after configuring on the respective port and restarting the EtherCAT system or reloading the configuration in Config mode; see Activating the configuration.

PDO Assignment 1:
Illustration of the process data allocation, showing as example SM3 inputs of EJ6224

SM3, PDO Assignment 0x1C13

Index

Size (byte.bit)

Name

PDO content

0x1A81

2.0

DeviceState Inputs Device

Index 0xF101:0D - Device Diag
Index 0xF101:10 - Device State

0x1A80

4.0

DeviceState Inputs

Index 0xF100:01 - State Ch1
Index 0xF100:02 - State Ch2
Index 0xF100:03 - State Ch3
Index 0xF100:04 - State Ch4

0x1A00

0.0 - 32.0

Port 1 Process Data

IO-Link device-specific / only active after configuration

0x1A01

0.0 - 32.0

Port 2 Process Data

IO-Link device-specific / only active after configuration

0x1A02

0.0 - 32.0

Port 3 Process Data

IO-Link device-specific / only active after configuration

0x1A03

0.0 - 32.0

Port 4 Process Data

IO-Link device-specific / only active after configuration

PDO Assignment 2:

Process data representation

If data types are used that don't conform to IEC61131-3, they are represented as octed strings.

Via index 0xF100:0n the status of the IO-Link ports 1-4 is indicated.
The indices 0xF101:xx provide general diagnostic data.

Index

Size (byte.bit)

Name

Meaning

0xF101:0D

0.1

Device Diag

Occurrence of events (on the device side) is reported via a status bit

0xF101:10

0.1

Device State

Interruption of communication with one of the devices is reported via a status bit

0xF100:01

1.0

State Ch.1

See table “Meaning Status byte Ch. 1 - Ch. 4”

0xF100:02

1.0

State Ch.2

0xF100:03

1.0

State Ch.3

0xF100:04

1.0

State Ch.4

The status bytes are divided into two nibbles.

Meaning Status byte Ch. 1 - Ch. 4

Low nibble:

0x_0 = Port disabled
0x_1 = Port in std dig in
0x_2 = Port in std dig out
0x_3 = Port in communication OP
0x_4 = Port in communication COMSTOP /  dig in Bit (only in std. IO Mode)
0x_5 = not defined
0x_6 = not defined
0x_7 = not defined
0x_8 = Process Data Invalid Bit

Combinations are possible and are displayed as addition of the values (s. note)

Higher nibble:

0x1_ = Watchdog detected
0x2_ = internal Error
0x3_ = invalid Device ID
0x4_ = invalid Vendor ID
0x5_ = invalid IO-Link Version
0x6_ = invalid Frame Capability
0x7_ = invalid Cycle Time
0x8_ = invalid PD in length
0x9_ = invalid PD out length
0xA_ = no Device detected
0xB_ = error PreOP/Data storage

Combinations are possible and are displayed as addition of the values (s. note)

PDO Assignment 3:

Addition of the values in case of simultaneously occurring diagnostic messages

If messages occur simultaneously, the value is displayed as a sum in the Status byte of the relevant channel.

  • Often for example 0x03 “Port in communication OP” and 0x08 “Process Data Invalid Bit” occur simultaneously:
    0x03 + 0x08 = 0x0B (11dec)
  • The value 0x0B (11dec) is displayed in the Status byte.