Configuration data vendor-specific
Index 80nF AO vendor data (for 0 ≤ n ≤ 3), channel 1 - 4
Code word The vendor reserves the authority for the basic calibration of the modules. The code word is therefore at present reserved. |
Index (hex) | Name | Meaning | Data type | Flags | Default |
---|---|---|---|---|---|
80nF:0 | AO vendor data | Max. Subindex | UINT8 | RO | 0x02 (2dec) |
80nF:01 | Calibration offset | Vendor calibration offset | INT16 | RW | 0x0000 (0dec) |
80nF:02 | Calibration gain | Vendor calibration gain | UINT16 | RW | 0xFFFF (65535dec) |