EJ2502 - 2-Channel pulse width output module 24 V DC

EJ2502 - Technical data

 
 
 
 
 
Technical data
EJ2502
Number of outputs
2
Rated load voltage
24 VDC (-15%/+20%)
Load type
ohmic, inductive, lamp load
Distributed Clocks
-
Output current (per channel)
max. 0.5 A (short-circuit proof, 1 A driver component)
Base frequency
1 .. 20 kHz, 250 Hz default
Duty factor
0 .. 100%
Resolution
9 .. 15 Bits
Switching times
TON > 750 ns, TOFF >500 ns
Power supply for electronics
via the E-bus
Current consumption via E-bus
typ. 110 mA
Electrical isolation
500 V (E-bus/field voltage)
Load voltage current consumption
typ. 10 mA + load
Permissible ambient temperature range during operation
-25°C .. + 60°C (extended temperature range)
Permissible ambient temperature range during storage
-40°C .. + 85°C
Permissible relative humidity
95%, no condensation
Operating altitude
max. 2,000 m
Dimensions (W x H x D)
approx. 12 mm x 66 mm x 55 mm
Gewicht
approx. 30 g
Mounting
on signal distribution board
Pollution degree
2
Installation position
1 and 4
Color coding
red
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27 (with corresponding signal distribution board)
EMC immunity / emission
conforms to EN 61000-6-2/EN 61000-6-4 (with corresponding signal distribution board)
Protection class
EJ module: IP20,
EJ system: dependent on signal distribution board and housing
Approval
CE, UL
 
 
CE approval
The CE Marking refers to the EtherCAT plug-in module mentioned above.
If the EtherCAT plug-in module is used in the production of a ready-to-use end product (PCB in conjunction with a housing), the manufacturer of the end product must check compliance of the overall system with relevant directives and CE certification.
To operate the EtherCAT plug-in modules, they must be installed in a housing.