EJ1809, EJ1819, EJ1889 - LEDs

EJ1809, EJ1819, EJ1889 - LEDs 1:
EJ1809, EJ1819, EJ1889 - LEDs

LED

Color

Display

State

Description

RUN

green

off

Init

State of the EtherCAT State Machine: INIT = initialization of the plug-in module

flashing

Pre-Operational

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set

Single flash

Safe-Operational

State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels and the distributed clocks.
Outputs remain in safe state

on

Operational

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible

flickering

Bootstrap

State of the EtherCAT State Machine: BOOTSTRAP = function for firmware updates of the plug-in module

Up

green

off

-

No 24VDC power supply connected

on

-

24VDC power supply connected

I1 .. I16

green

off

-

EJ1809, EJ1819: Signal voltage "0" (-3 V .. 5 V)

EJ1889: Signal voltage "0" (18 V .. 30 V)

on

-

EJ1809, EJ1819: Signal voltage "1" (11 V .. 30 V)

EJ1889: Signal voltage "1" (0 V .. 7 V)