Technical data

Technical data, dimensions and weights.

 

CX8190

Dimensions (W x H x D)

71 mm x 100 mm x 73 mm

Weight

230 g

Technical data, general data.

Technical data

CX8190

Processor

ARM Cortex™-A9, 800 MHz 32-bit

Main memory

512 MB DDR3-RAM

Flash memory

MicroSD card (ATP) 512 MB (optionally 1, 2, 4, 8 GB)

Interfaces

1 x RJ45 10/100 MBit/s

Bus interface

2 x RJ45 (switched)

Protocol

Real-time Ethernet, ADS UDP, ADS TCP, EAP (EtherCAT Automation Protocol)

Persistent memory

1-second UPS integrated

Power supply

24 VDC (-15%/+20%)

Max. power consumption

4 W

Max. power consumption (with UPS charging)

9 W

Dielectric strength

500 V (supply / internal electronics)

Operating system

Microsoft Windows Embedded Compact 7

Control software

TwinCAT 3, licenses not included

Diagnostic LED

1 x TC Status, 1 x WD LED, 1 x ERR LED

Clock

internal battery-backed clock (RTC) for time and date (battery exchangeable)

Approvals

CE, UL

Technical data, I/O terminals.

Technical data

CX8190

I/O connection

via power supply terminal (E-bus or K-bus, automatic recognition)

Power supply for I/O terminals

max. 2 A

Power contacts current load

max. 10 A

Process data on the K-bus

max. 2 kB In and 2 kB Out

max. number of terminals (K-bus)

64 (255 with K-bus extension)

max. number of terminals (E-bus)

up to 65534 terminals.

Technical data, environmental conditions.

Technical data

CX8190

Ambient temperature during operation

-25° C ... +60° C

Ambient temperature during storage

-40° C ... +85° C
see notes under: Transport and storage

Relative humidity

95% no condensation

Vibration resistance

conforms to EN 60068-2-6

Shock resistance

conforms to EN 60068-2-27

EMC immunity

conforms to EN 61000-6-2

EMC emission

conforms to EN 61000-6-4

Protection rating

IP20

Technical data, Ethernet interface X001.

Technical data

Description

Data transfer medium

4 x 2 twisted pair copper cables category 5 (100 MBit/s)

Cable length 

100 m from switch to CX8190

Data transfer rate

10/100 MBit/s

Topology

star wiring

Protocols

all non-real-time-capable protocols that are based on TCP or UDP and require no real-time extension

Technical data, Ethernet interfaces X101/X102.

Technical data

Description

Data transfer medium

4 x 2 twisted pair copper cables category 5 (100 MBit/s)

Cable length 

100 m from switch to CX8190

Data transfer rate

100 Mbit/s

Topology

star wiring, line topology

Protocols (real-time)

RT-Ethernet, EAP (publisher/subscriber)

Protocols (non-real-time)

all non-real-time-capable protocols that are based on TCP or UDP and require no real-time extension