Replace the fan cartridge

Replace the fan cartridge 1:

Service life

The fan cartridge must be replaced every 5 years. Spare fan cartridges can be ordered from Beckhoff Service.

Replace the fan cartridge of the CX20x2 if:

In a CX20x2 Embedded PC the fan speed is controlled depending on the temperature.

In the CX20x2 the fan control and speed depend on the temperature.

Temperature

Fan control

Fan speed

up to 30 °C

30 %

3400 rpm

30 °C … 75 °C

30 % … 100 %, linear control

3400 rpm ... 6000 rpm, linear regulated

above 75 °C

100 %

6000 rpm

Use the IPC diagnostics and monitor the fan speed to determine a fan fault.

Access to the fan status is described in the documentation for the IPC diagnostics:
https://download.beckhoff.com/download/Document/ipc/industrial-pc/Beckhoff-Device-Manager_en.pdf

Replace the fan cartridge as follows:

1. Open the front flap.
2. Pull the old fan cartridge from the housing.
Replace the fan cartridge 2:
3. Push the new fan cartridge into the housing, with the contacts first.
The guide rails at the fan match the guide rails in the housing.
Replace the fan cartridge 3:
Close the front flap. You have successfully changed the fan cartridge if the fan starts up again.