Technical data

Technical data, dimensions and weights.

 

CX2042

CX2062

CX2072

Dimensions (W x H x D)

204 mm x 99 mm x 91 mm

Weight

approx. 1650 g

Technical data, general data.

Technical data

CX2042

CX2062

CX2072

Processor

Intel® Xeon® D-1527 2.2 GHz, 4 cores

Intel® Xeon® D-1548 2.0 GHz, 8 cores

Intel® Xeon® D-1567 2.1 GHz, 12 cores

RAM

8 GB DDR4 RAM (optionally expandable)

Flash memory

Plug-in for CFast card, card not included

NOVRAM integrated

128 kB

Power supply

24 V DC (-15 %/+20 %)

max. power consumption

95 W

103 W

131 W

Dielectric strength

500 V (supply / internal electronics)

Operating system

Microsoft Windows 10 IoT Enterprise LTSB

Control software

TwinCAT 3

Diagnostics LED

1 x power, 1 x TC status, 1 x flash access, 2 x bus status

Clock

Internal battery-backed clock for time and date (battery replaceable)

Approvals

CE, UL

Technical data, I/O terminals.

Technical data

Description

I/O connection

via power supply unit (E-bus or K-bus, automatic detection)

Power supply for I/O terminals

max. 2 A

Power contacts current loading

max. 10 A

Process data on the K-bus

max. 2048 bytes input and 2048 bytes output

max. number of terminals (K-bus)

64 (255 with K-bus extension)

max. number of terminals (E-bus)

up to 65534 terminals.

Technical data, environmental conditions.

Technical data

Description

Ambient temperature during operation

-25 °C ... +50 °C

Ambient temperature during storage

-40 °C ... +85 °C
see notes under: Transport and storage

Relative humidity

95 % no condensation

dynamic strength

according to EN 60068-2-6

Shock resistance

according to EN 60068-2-27

EMC immunity

according to EN 61000-6-2

Electromagnetic emission

according to EN 61000-6-4

Protection class

IP 20

Technical data, graphic specifications.

Technical data

Description

Graphic system

AMD E8860

Graphic memory

2 GB GDDR5

Graphics clock frequency

625 MHz

Shader model

5.0

DirectX

12

OpenGL

4.5

Technical data, interfaces.

Technical data

Description

LAN

2 x RJ 45, 10/100/1000 Mbit/s

USB

4 x USB 3.0 each rated at 900 mA, type A

DVI-I

Resolution on the monitor in pixels:
640 x 480 to 1920 x 1200

Technical data, optional interfaces.

Technical data

Description

DVI-D

Resolution on the monitor in pixels: 640 x 480 to 1920 x 1200

DisplayPort

Resolution on the monitor in pixels: max. 2560x1600

RS232

D-Sub plug, 9-pole
Electrical isolation 500 V

RS422/RS485

D-Sub plug, 9-pole
Electrical isolation 500 V

EtherCAT slave

2 x RJ 45, EtherCAT IN and OUT
100 Mbaud

PROFIBUS

D-Sub plug, 9-pole
9.6 kbaud to 12 Mbaud

CANopen

D-Sub plug, 9-pole
10 kbaud to 1,000 kbaud

PROFINET RT

2 x RJ-45 switches