The Bus Coupler's UserPrmData

The following settings can be made in the Bus Coupler's UserPrmData. So that a more easily understood GSD file is obtained in 90% of applications, some of the settings are only contained in text form in the Extended GSD file, and these are indicated in the last column by Extended. The standard settings are contained both in the standard and the extended GSD file.

Byte

Bit

Value

Description

GSD file

0

7

0bin

MSAC_C1 connection is not active (default)

Standard

1bin

MSAC_C1 connection is active (see DPV1)

1

0

0bin

CfgData checking is active (default)

Extended

1bin

CfgData checking deactivated (see Deactivating the CfgData checking)

2

3

0bin

Diagnostic data is transferred in a form compatible with the BK3100

Extended

1bin

Diagnostic data is transferred in a form compatible with DPV1 (default)

3

3

0bin

K-bus cycle counter is not active (default)

Extended

1bin

K-bus cycle counter is active (see K-bus cycle)

3

4

0bin

Multi-configuration mode is not active (default)

Extended

1bin

Multi-configuration mode is active (see Multi-configuration mode)

3

5

0bin

Dummy output byte not active (default)

Extended

1bin

Dummy output byte is active (see K-bus cycle)

3

6

0bin

MCM startup "Static diagnostics"
In multi-configuration mode, the coupler sets the Stat_Diag bit in the diagnostic data if the configuration is not consistent, and does not yet enter data exchange (default).

Extended

1bin

MCM startup "Data exchange without K-bus"
In multi-configuration mode the coupler also enters data exchange even when the configuration is not consistent, although K-bus cycles are not yet executed (see Multi-configuration mode)

5

0

0bin

2-byte PLC interface not activated (default)

Extended

1bin

2-byte PLC interface is active (see 2-byte PLC interface)

7

0

0bin

Response to K-bus error: Manual K-bus reset (default) (see K-bus interruption)

Standard

1bin

Response to K-bus error: automatic K-bus reset

7

1

0bin

Terminal diagnosis is not active (default) (see Terminal diagnosis)

Standard

1bin

Terminal diagnosis is active

7

4

0bin

Diagnostic data for digital terminals included in process image (default) (see Terminal diagnosis)

Standard

1bin

Diagnostic data of digital terminals not in the process image (default)

9

2

0bin

Analog modules are mapped in compact form (only showing the input and/or output user data) (this is the default, only relevant when CfgData checking has been deactivated, otherwise the terminals are set by means of the CfgData) (see Deactivation of CfgData checking)

Extended

1bin

Analog modules are mapped in complex form (with control/status for register access and with the same data length in inputs and outputs) (only relevant when CfgData checking has been deactivated, otherwise the terminals are set by means of the CfgData)

9

3

0bin

Representation in INTEL format

Standard

1bin

Representation in Motorola format (default)

9

4

0bin

K-bus mode slow FreeRun (default) (see K-bus cycle)

Standard

1bin

K-bus mode fast FreeRun

9

5

0bin

WORD alignment inactive (default)

Extended

1bin

WORD alignment active (see WORD alignment)

9

6

0bin

K-bus mode is synchronous (see K-bus cycle)

Standard

1bin

K-bus mode FreeRun (default)

Byte

Bit

Value

Description

GSD file

10

0-1

00bin

Reaction to PROFIBUS error: K-bus cycle is abandoned (default, digital outputs become 0, complex outputs are set to a configured substitute value) (see Reaction to PROFIBUS errors)

Standard

01bin

Reaction to PROFIBUS error: K-bus outputs become 0

10bin

Reaction to PROFIBUS error: K-bus outputs remain unchanged

10

2-3

00bin

Reaction to K-bus error: DP data exchange is abandoned (default) (see K-bus interruption)

Standard

01bin

Reaction to K-bus error: DP inputs set to 0

10bin

Reaction to K-bus error: DP inputs remain unchanged

11

3-6

X

Maximum length of the diagnostic data. Allowed values: 16, 24, 32, 40, 48, 56, 64 (see Terminal diagnosis)

Extended

12

0-1

0bin

If K-bus mode is synchronous: Standard synchronous mode (default) (see K-bus cycle)

Extended

01bin

If K-bus mode is synchronous: synchronous mode with optimized input update (one cycle)

10bin

If K-bus mode is synchronous: synchronous mode with optimized input update (two cycles)

12

4-7

0bin

Maximum DP buffer lengths not changed

Extended

12

4-7

15

The maximum DP buffer lengths are changed using the values from UserPrmData 37-40 (see Multi-configuration mode)

Extended

13

0-7

X

Delay time (in µs) high byte (see K-bus cycle)

Extended

14

0-7

X

Delay time (in µs) low byte (see K-bus cycle)

Extended

15-30

0-7

X

Assignment of Bus Terminals 1 to 64 (see Multi-configuration mode)

Extended

31-36

0-7

-

Reserved

Extended

37

0-7

X

Maximum length of the input data (see Multi-configuration mode)

Extended

38

0-7

X

Maximum length of the output data (see Multi-configuration mode)

Extended

39

0-7

X

Maximum length of the diagnostic data (see Multi-configuration mode)

Extended

40

0-7

X

Maximum length of the configuration data (see Multi-configuration mode)

Extended

41-56

0-7

X

Assignment of terminals 65 to 128 (see Multi-configuration mode)

Extended