Probe Unit

The latch/probe functionality implemented in the AX5000 is compliant with the probe functionality defined in the Sercos specification (v2.4).

 IDNs involved

Probe Unit 1:

IDN-description

A detailed description of the individual IDNs can be found the following document: AX5000 - IDN Descriptions.

IDN

Name

S-0-0130

Probe 1 value positive edge

S-0-0131

Probe 1 value negative edge

S-0-0169

Probe control parameter

S-0-0170

Probing cycle procedure command (pc)

S-0-0179

Probe status

S-0-0405

Probe 1 enable

S-0-0409

Probe 1 positive latched

S-0-0410

Probe 1 negative latched

P-0-0154

Feedback 1 reference signal

P-0-0250

Probe 1 value source

P-0-0251

Probe 1 logic configuration

P-0-0252

Probe 1 logic state

P-0-0253

Probe 1 time positive edge

P-0-0254

Probe 1 time negative edge

P-0-0255*

Probe 1 time difference: reference switch to index

P-0-0256*

Probe 1 data

*) In preparation.

Functioning

Probe Unit 2:

The signal source (reference signal feedback, RSF) is selected with IDN P-0-0251. The reference signal of the encoder system or a simple digital input or a combination of 2 inputs can be selected.

The following signals are available for selection:

Multiplexer 1, see drive parameter description (IDNs)

P-0-0251.Mux1

Input

0

DigIn 0

1

DigIn 1

2

DigIn 2

3

DigIn3

4

DigIn4

5

DigIn5

6

DigIn6

7

DigIn7

Multiplexer 2

P-0-0251.Mux1

Input

0

DigIn 0

1

DigIn 1

2

DigIn 2

3

DigIn3

4

DigIn4

5

DigIn5

6

DigIn6

7

DigIn7

8

Reference Signal Feedback Front

9

Reference Signal Feedback Option Card

 

rsvd.

Reference Signal Feedback Front

P-0-0154

Input

0

Zero Index

1

Magnitude of sine signal

2

Magnitude of cosine signal

3

rsvd

The parameter P-0-0154.ThresholdVoltage can be used to modify the threshold level (if zero index is selected).

IDN P-0-0154 can only be edited in EtherCAT state PreOperational. In states SafeOperational and Operational this IDN is write-protected.

The selected signals are linked via the following logic:

Logic

P-0-0251.Logic

Logic output

0

Output Mux 1

1

Output Mux 2

2

Ouptut Mux 1 AND Output Mux 2

3

Output Mux 1 OR Output Mux 2

5

Output Mux 1 AND rising edge output Mux 2

Probe Value-Source

IDN P-0-0250 is used to select which value (e.g. actual position) is to be stored for the latch event.

P-0-0250

Source

0

Position feedback value 1 (S-0-0051)

1

rsvd

The command S-0-0170 is activated internally in the probe cycle, and the parameters of IDNs P-0-0250 and P-0-0251 are transferred internally. These two IDNs are write-protected if this command is active.

The probe unit is activated with IDN S-0-0405. If S-0-0405 is associated with a falling edge the result-registers are reset to 0.

IDN-S.0-0179 (or S-0-0409 and S-0-0410) indicates whether a latch event has occurred.

After a latch event the associated data are entered in IDNs S-0-0130, S-0-0131, P-0-0253, and P-0-0254.

Configuration sequence

  1. Feedback 1 reference signal (P-0-0154) (only possible in EtherCAT state PreOperational)
  2. Probe 1 value source (P-0-0250)
  3. Probe 1 logic configuration (P-0-0251)
  4. Start of "Probing cycle procedure commands" (S-0-0170)
  5. Probe control parameter (S-0-0169)
  6. Probe enable (S-0-0405)