S-x-0091 Bipolar velocity limit value

This parameter limits the velocity command value of the drive. This parameter defines the upper (positive) and lower (negative) limit. The lowest value of all set limits applies.

Attributes

Name

Value

Datatype

udec

Data length in bit

32

Decimal point

0

Min value

0

Default

53687091

Max value

894784853

Unit

rev/(230 ms)

Changeable in EtherCAT state

PreOp, SafeOp, Op

Cyclic transfer

No

Device parameter

No

Related to interface revision

No

S-x-0091 Bipolar velocity limit value 1:

Included in the “Parameter Set Switching” function group!

This IDN exists as S-0-0091 - S-7-0091. Ex factory, all values are identical.

S-x-0091 Bipolar velocity limit value 2:

For further information please look into the involved IDN:

S-0-0044, S-0-0045, S-0-0046

S-x-0091 Bipolar velocity limit value 3:

Additional functional description

AX5000 / parameter set switchover