S-0-0076 Position data scaling type

This parameter can be used to select different scaling types for the position signals. The drive represents associated parameters at the selected scale.

Attributes

Name

Value

Datatype

binary

Data length in bit

16

Decimal point

0

Min value

-

Default

10

Max value

-

Unit

-

Changeable in EtherCAT state

PreOP

Cyclic transfer

No

Device parameter

No

Related to interface revision

No

Bit pattern:

Bit

Meaning

0-2

Scaling method
Scaling method

0 = no scaling
1 = linear
2 = rotary

3

Scaling type
Scaling type

0 = preferred scaling
1 = parameter scaling

4

Units for linear / rotational scaling
Units for linear / rotational scaling

0= metre [m] / angle
1 = reserved

5

Reserved

6

Data reference
Data reference

0 = at the motor shaft
1 = at the load

7

Processing format
Processing format

0 = absolute format
1 = modulo format

8 - 15

Reserved

S-0-0076 Position data scaling type 1:

For further information please look into the involved IDN:

S‑0-0103, S-0-0079

S-0-0076 Position data scaling type 2:

Additional functional description

AX5000 - function descriptions / modulo