S-0-0160 Acceleration data scaling type

This parameter can be used to select different scaling types for the acceleration data in the drive. The drive represents associated parameters at the selected scale.

Attributes

Name

Value

Datatype

binary

Data length in bit

16

Decimal point

0

Min value

-

Default

10

Max value

-

Unit

-

Changeable in EtherCAT state

No

Cyclic transfer

No

Device parameter

No

Related to interface revision

No

In the AX5000, percentage scaling is selected via S-0-0086 "Torque/force data scaling type". S-0-0160 is therefore not evaluated.

Bit pattern:

Bit

Meaning

0 -2

Scaling method
Scaling method

0 = no scaling
1 = linear scaling
2 = rotary scaling
3 = ramp time (see S-0-0446)

3

Scaling type
Scaling type

0 = preferred scaling
1 = parameter scaling

4

Units for linear / rotational scaling
Units for linear / rotational scaling

0 = meter / radian
1 = inch / reserved

5

Time unit
0 = seconds
1 = reserved

6

Data reference
0 = at the motor shaft
1 = at the load

7 - 15

Reserved

S-0-0160 Acceleration data scaling type 1:

For further information please look into the involved IDN:

S-0-0086, S-0-0160