S-0-0159 Monitoring window

This parameter specifies the maximum permissible deviation between the set and actual positions. If this difference, which is also referred to as position lag, exceeds the value specified in this parameter, the drive sets the C1D error bit 11 of S-0-0011.

Attributes

Name

Value

Datatype

udec

Data length in bit

32

Decimal point

0

Min value

0

Default

1 048 575

Max value

4 294 967 295

Unit

inc

Changeable in EtherCAT state

PreOp, SafeOp, Op

Cyclic transfer

No

Device parameter

No

Related to interface revision

No

Following error monitoring in the AX5000 is only active if the value of S-0-0159 > 0. If the higher-level controller (NC) monitors the following error (S-0-0189), this parameter can be left at the "default" value of 1 048 575. If the controller does not deal with this task, a value adapted to the application must be specified here.

S-0-0159 Monitoring window 1:

For further information please look into the involved IDN:

S-0-0076, S-0-0079, S-0-0189