Disassembly
WARNING
Observe the discharge times of the capacitors
Keep to the waiting times after disconnection from the supply network:
- 30 minutes for AX8620 and AX8640
- 30 minutes for AX8108, AX8118 and AX8206
- 30 minutes for AMP8620-2005-0x00
- 30 minutes for AMP8805-1000-0000
- 30 minutes for AX8831
- 30 minutes for AX8832
- 5 minutes for AX5101 to AX5125 and AX5172
- 15 minutes for AX5140, AX5160 and AX5172
- 30 minutes for AX5190 and AX5191
- 45 minutes for AX5192 and AX5193
- There is still a life-threatening voltage of > 848 VDC on the capacitors after disconnection from the supply network. Serious or even fatal injuries may result if this is ignored.
Do not remove components from the products Only Beckhoff Automation GmbH & Co. KG is permitted to remove components. Contact Beckhoff Service if you have any questions. |
Removing the brake resistor from the machine
- Remove cables and electrical connections
- Loosen and remove the brake resistor fixing screws
- Transport the brake resistor to the workplace or put it into storage